TROUBLESHOOTING
Page 2
1.1 SYMPTOM - W
HEN
DC P
OWER
IS
TURNED
O
N
,
OPERATOR
CANNOT
TAKE
COMMAND
AT
ONE
S
TATION
(
BOTH
P
ORT
AND
S
TARBOARD
FOR
TWIN
SCREW
).
Cause:
A)A corroded or loose electrical connection.
B) Incorrectly wired eight-conductor cable.
C) Defective Control Head.
Remedy
:
A)At the Control Head verify crimps and screws are tight. Verify
the station connections at the Processor. Tighten or re-crimp as
necessary.
B) Rewire the cable connections as shown on Appendix B Draw-
ing and Paragraph 5.3.3 of the main manual. Correct as neces-
sary.
C) Verify the voltage between the red and orange wires (Terminals
3 and 4). The reading should be 4.80 to 5.00 volts DC. Verify
the voltage at Terminals 3 and 4 while depressing the transfer
button. The voltage reading should be less than 0.50 volts DC.
If the voltage remains near 5.00 volts, the Control Head needs
repair.
1.2 SYMPTOM - O
NE
SIDE
WILL
NOT
TAKE
COMMAND
WHEN
DC P
OWER
IS
FIRST
TURNED
ON.
Cause
:
A)Port and Starboard power sources do not have a common
ground (only the Starboard would be unable to take command).
B) Miswired eight-conductor cable.
C) Defective Control Head potentiometer.
Remedy
:
A)Verify that the negative terminal connections of both batteries
are to a common point. If not, connect both to a common point.
NOTE: Always check the other Stations, to see if the symptom can be repeated.
Содержание ClearCommand
Страница 56: ......
Страница 57: ...APPENDIX A 1 ...
Страница 58: ......
Страница 60: ...Appendix A 6 20 01 Page 2 ...
Страница 63: ...Page 5 ...
Страница 64: ...Page 6 ...
Страница 68: ...Page 10 ...
Страница 70: ...Page 12 ...
Страница 72: ...Page 14 ...
Страница 78: ...Page 20 ...
Страница 82: ...Page 24 ...
Страница 85: ...APPENDIX B 1 ...
Страница 86: ......
Страница 97: ...APPENDIX C 1 ...
Страница 98: ......
Страница 99: ...Drawing 11202F 1 ...
Страница 100: ... ...
Страница 101: ...Drawing 11202F 2 ...
Страница 102: ... ...
Страница 103: ...Drawing 11202F 3 Notes Page ...
Страница 104: ... ...