30 V00 Installation and operating instructions
5.4.6 AC circuit breaker
No consumer load should be applied between the AC circuit breaker and the inverter.
Use dedicated circuit breakers with load switch functionality for load switching. The
selection of the AC circuit breaker rating depends on the wiring design (wire
cross-section area), cable type, wiring method, ambient temperature, inverter current
rating, etc. Derating of the AC circuit breaker rating may be necessary due to
self-heating or if exposed to heat.
The maximum output current of the inverters can be found in the following table.
Type
Zeverlution Pro 33K
Max. output current
48A
Recommended fuse type gL/gG or comparable
automatic circuit breaker rating
63A
Danger to life due to fire!
• You must protect each inverter with an individual AC circuit breaker in
order to ensure that the inverter can be disconnected safely.