background image

Smart Connect Multi-loop Installation Manual

 

 
www.zetaalarmsystems.com

 

Introduction

 

About the Smart Connect Multi-loop Fire Alarm System 

The Smart Connect Multi-loop Control Panel is a powerful intelligent fire alarm control system with a user friendly 4.3 inch touch 
screen display, which has been designed to provide reliable life safety and property protection, while also being easy to install, 
commission and operate. The Smart Connect Multi-loop system is totally modular which enables it to satisfy any size building fire alarm 
needs. 
 
By adding intelligent loop modules, the Smart Connect Multi-loop can be upgraded to support up to 3000 addressable devices spread 
across a flexible number of loop cards (maximum of twelve loop cards). The system can also be expanded by adding Form C relay 
output modules, network interface modules, alarm circuit modules, and zone monitor modules for conventional detectors and devices. 
 
The Smart Connect Multi-loop 

system’s touchscreen interface is designed to m

ake status information clear, and system control 

functions simple to operate. Through the use of function buttons on the systems display 

the user can easily “

SILENCE BUZZER

”, “

STOP 

SOUNDERS

” or “

START SOUNDERS

”, or “

RESET

” the system. The system status presentation is structured 

to allow the different types of 

system events (Alarms, technical alarms, and faults) to be viewed independently. Each system event presents the user with a message 
describing the location of the alarm report and the type of event (manual alarm, smoke, or heat). If additional details about the nature 
of the alarm report or its location are required, the user can add a text label to the device or zone.  
 
The 32-bit microcontroller (MCU) at the heart of Smart Connect Multi-loop rapidly processes logical decisions based on the status of 
the smoke detection and other initiating devices to control the system outputs. The Windows based software 

‘Smart Configurator’

 is 

used to configure the system’s operation based on the customer specified operating requirements

, and reduce 

commissioning/installation times. 
 
The Smart Connect Multi-loop system continuously checks all software and hardware for proper operation. It checks all control panel 
electronic hardware, system memory components, and the system program. A hardware watchdog circuit is provided to ensure that 
System programs are functioning properly. If a problem develops with the program or processor, the watchdog circuit places the 
System into a fault condition and resets it. 
 
The Smart Connect Multi-loop system is equipped with a backup microprocessor on its termination board. To ensure reliable 
operation, if the 

main panel’s CPU

 stops, the backup CPU will take over and allow the system to still be able to detect and annunciate 

alarms. 
The fire alarm operation is always processed as the highest priority over all other operating modes. 
 
 

Overall Features 

 

Modular construction allows a panel to be specified using just the required modules. 

 

Up to 4, 6 or 12 Loop modules (depending on panel model). 

 

4.3” colour touch screen display

 

Capacity for up to 26 intelligent modules (depending on panel model).   

 

Full system redundancy. 

 

Extensive Day/Night mode programming. 

 

Full cause & effect programming via front of panel or 

the ‘Smart Configurator’ P

C software. 

 

250 ZETA addressable MKII devices per loop card. 

 

254 available programmable zones. 

 

Up to 64 panel peer-to-peer network. 

 

Positive Alarm Sequence. 

 

Alarm Verification. 

 

Alarm circuit special application 24V mode. 

 

15A power supply. 

 
 
 
 
 
 

Содержание SMARTCONNECT SMART6

Страница 1: ...GLT 261 7 3 Doc GLT 261 7 1 Issue W I P Date 25 08 2018 Doc GLT 261 7 10 Issue 001 Date 14 08 2020 MULTI LOOP PANEL Installation Manual...

Страница 2: ...ble Grounding 13 Mains Wiring 13 Battery Wiring 15 Assembling the panel 18 Initial Power Up 19 Module Installation 19 TRM RJ45 Port Address Designation 20 Securing the modules 20 Before Powering the P...

Страница 3: ...ifications 36 Compatible Loop Card Devices 36 Power Supply 37 PSU Specifications 37 PSU Fuses 38 Power Supply Status Indications 38 Power Supply Signals 38 Panel Printer 39 Loading Replacing the Print...

Страница 4: ...l to the device or zone The 32 bit microcontroller MCU at the heart of Smart Connect Multi loop rapidly processes logical decisions based on the status of the smoke detection and other initiating devi...

Страница 5: ...Engineer Password Default 9999 and press Menu Access Icon Configure loops Assign zones Assign Text to each point Modify Alarm Operation Programming Configure network if fitted System Diagnostics LED...

Страница 6: ...ired conventional inputs and outputs and addressable inputs and outputs may be grouped together to form logical zones Wiring Styles Loop Circuits have a redundant pathway powered from both sides of th...

Страница 7: ...a 400W 15A PSU Space for 2 x 14Ah batteries SMART10 64 W 500mm x H 600mm Space for up to 10 small modules Equipped with 64 zone LED expansion Supplied with a 400W 15A PSU Space for 2 x 38Ah batteries...

Страница 8: ...HF MKII AHF CS90 ZAI MI ZAIO MI ZAZM MI ZAIO 230 ZASC MI MKII SSB MKII AXT MKII AXTB ZRAP ZRAPB All are EN54 approved SCM ACM Alarm Circuit Module The plug in alarm circuit module provides power for a...

Страница 9: ...ies etc Input Voltage 23 7VDC Nominal Wiring Class 6 x Class B Quiescent Current 30V 39 3mA Input Max Impedance 10 Input End of Line 4K7 Alarm Triggering Resistor 1K SCM ZMM Zone Monitor A zone monito...

Страница 10: ...RT 10 665mm 535mm 505mm 200mm 170mm 635mm 26 8 4 2 x 38Ah SMART 26 665mm 975mm 945mm 200mm 170mm 635mm 64 28 20 2 x 38Ah Panel Construction Details All components are manufactured from Zintec Large an...

Страница 11: ...panel must be in a clean dry position which is not subject to excessive shock or vibration and at least 2 meters away from pager systems or any other radio transmitting equipment The operating tempera...

Страница 12: ...Smart Connect Multi loop Installation Manual www zetaalarmsystems com 12 Fig 2 Fig 3...

Страница 13: ...l damage Also the power supply and termination board should be removed and stored in a safe place This would also help while fixing the back box to the wall Cable Grounding The panel is provided earth...

Страница 14: ...ns Earth cable is connected to the PSU s Earth terminal The incoming mains cable should be kept separate from the loop card cables to help minimise mains interference It is advisable to apply power to...

Страница 15: ...ration 0 25A2s 230Vac Cold Start 3 15A 230 V AC Battery Wiring The SMART Connect Multi loop panel uses two 12 Volt batteries wired in series to give a 24 Volt back up supply The ve of one battery is c...

Страница 16: ...harger Current Max Battery Size Fuse Installed SMART6 29 5V DC 27 6V DC 400W 1 1A 2 x 12V 14 Ah 5A SMART10 29 5V DC 27 6V DC 400W 2 2A 2 x 12V 38 Ah 8A SMART26 29 5V DC 27 6V DC 400W 2 2A 2 x 12V 38 A...

Страница 17: ...Smart Connect Multi loop Installation Manual www zetaalarmsystems com 17...

Страница 18: ...ed and connect to the panel s motherboard with a small RJ45 cable supplied with the module The Base panel is available in 3 sizes SMART6 SMART10 SMART26 The above diagrams show the port addresses for...

Страница 19: ...now be turned off and the modules can be fitted Module Installation The Smart Multi loop panel uses the expansion port number to reference modules It is recommended that any Loop Card modules are fitt...

Страница 20: ...e first module and after the last module on each rail Before Powering the Panel On 1 To prevent the risk of a spark do not connect the batteries Only connect the batteries after powering on the system...

Страница 21: ...ected modules are fitted and that all module cables are correctly inserted Note that the panel will need at least one module fitted to run The panel has detected a new module added to a port that was...

Страница 22: ...e EARTH Green NEG POS NEG POS BLACK RED BATTERY CABLE OBSERVE POLARITY RED BLACK SCM LCM S CM A CM SCM ZMM SCM MIM SCM RM SCM NM SCM PM A A B B NAC1 A A A A C C C C C C C C C C C C C C C ZM1 ZM2 ZM3 Z...

Страница 23: ...tems com 23 SCM ACM Field Wiring Connections Typical Wiring Diagram Class B Zeta Conventional Sounders Typical Wiring Diagram Class B Bell Devices NOTE When an ACM is configured as a bell output the 2...

Страница 24: ...e Regulated 24V DC Power limited Supervised Maximum Alarm Circuit Current 2 x 500mA Maximum Aux 24V Current 2 x 400mA Maximum RMS current for a single sounder device 350mA Maximum Line Impedance 3 6 t...

Страница 25: ...output Please refer to the device manuals to calculate the maximum number allowed on each alarm circuit SCM MIM Field Wiring Connections Wiring Recommendations for Input Circuits SCM MIM Wire Gauge AW...

Страница 26: ...Form C Switching Capacity 5 A 30VDC resistive 5 A 250VAC general use Circuit Type Power limited Not Supervised Modes Common alarm Common fault Common tech alarm or Programmable Recommended cable sizes...

Страница 27: ...iring Class 6 x Class B circuits Recommended cable sizes 22 AWG to 14 AWG 0 3mm2 to 2 5mm2 End of Line Resistor 4K7 Alarm Trigger Resistor 1K Compatible Devices MKII OP MKII HR MKII HF MKII HF CS90 MK...

Страница 28: ...allation Manual www zetaalarmsystems com 28 SCM NM Field Wiring Connections Ring Topology Bus Topology NOTE It is recommended to install the network in a ring topology for protection against open circ...

Страница 29: ...iring SCM NM The SMART Connect Multi loop network can support up to 64 panels SCM NM Specifications Network Module SCM NM Maximum Network Size 64 Nodes Maximum Distance Between Nodes 1KM with screened...

Страница 30: ...r 2 or more detection zones short circuit isolators or devices with built in short circuit isolators such as interfaces should be fitted to the zone boundaries to prevent a single short circuit affect...

Страница 31: ...ngs PVC plastic foam and all similar materials which produce small visible particles 0 5 to 10 m MKII AHR MKII AHFand MKII AHF CS90 MKII AHR MKII AHF and MKII AHF CS90 The Fyreye MKII Rate of Rise hea...

Страница 32: ...MKII AHF CS90 MKII AHR and MKII AOH detector series heads The series includes MKII CB which is a 4 inch standard base and MKII CB D which is 4 inch deep base MKII CB MKII CB D are supplied with 5 ter...

Страница 33: ...ondition Typical output triggering includes controlling lift operation during an alarm starting fire pump stopping ventilation fans etc ZAIO MI typical wiring diagram E g connecting to a door magnet Z...

Страница 34: ...rs have been activated or extinguisher level monitoring in Gas Extinguishing systems etc Module is provided with a loop short circuit isolator and with a voltage free single pole change over mains rat...

Страница 35: ...or a clean first fix The AXTB beacon has a coverage pattern of W 3 1 9 1 MKII AXT MKII AXTB typical wiring diagram E g Loop wiring ZRAP ZRAPB ZRAPB R pictured ZRAP ZRAPB The Raptor addressable sounder...

Страница 36: ...Smoke Heat A1R Detector With Built In Isolator MKII AOHI MKII Addressable Fixed Heat Only A2S Detector With Built In Isolator MKII AHFI MKII Addressable Fixed Heat Only CS Detector With Built In Isola...

Страница 37: ...ltage 120 230 VAC 120 230 VAC 120 230 VAC Power Supply Rating 400 Watts 400 Watts 400 Watts DC Output Voltage 30 VDC 30 VDC 30 VDC Maximum Output Current 11 1 Amp 11 1 Amp 11 1 Amp Battery Voltage 27...

Страница 38: ...NC C in normal operating condition When there is a fault condition on the mains power continuity is switched to NO C Relay is normally energized and fail safe as the relay will change over in the eve...

Страница 39: ...cification PLUS2 Paper Type Thermal Paper Roll Paper Width 57mm Roll Diameter 50mm Roll Length 30m See note Paper Weight 55 to 70gsm To change the printer roll proceed as follows Every time the paper...

Страница 40: ...Reception errors Parity frame error overrun error ON Flash x 6 Green Command is not recognised ON Flash x 7 Green Command reception has timed out Printer Maintenance The regular cleaning of the panel...

Страница 41: ...Output B Auxiliary Power 29V 1A 29V 1A 29V 1A Output C Control Panel Power 29V 7 5A 29V 7 5A 29V 7 5A Output D Control Panel Power 29V 7 5A 29V 7 5A 29V 7 5A Display LCD Display 4 3 Resistive touch sc...

Страница 42: ...c Other Functions outside EN54 USB port For PC configuration and software upgrading RS485 Network Repeater connection TCP IP Ethernet connection Remote access Programmable Cause Effect on Outputs Phas...

Страница 43: ...S C Isolator 3 5 13 2 ZAIO 230 MKII Addressable Mains switching Input Output Module 1 5 4 6 SMM B Special Mini Modules White Beam Detector 1 1 12 MKII SSB MKII Sandwich Sounder No Address Required 0...

Страница 44: ...F ON ON 88 ON ON ON OFF OFF ON OFF ON 3 OFF OFF ON ON ON ON ON ON 46 ON OFF OFF OFF ON OFF ON ON 89 OFF ON ON OFF OFF ON OFF ON 4 ON ON OFF ON ON ON ON ON 47 OFF OFF OFF OFF ON OFF ON ON 90 ON OFF ON...

Страница 45: ...F ON OFF ON OFF ON OFF ON 128 ON ON ON ON ON ON ON OFF 171 OFF OFF ON OFF ON OFF ON OFF 214 ON OFF OFF ON OFF ON OFF OFF 129 OFF ON ON ON ON ON ON OFF 172 ON ON OFF OFF ON OFF ON OFF 215 OFF OFF OFF O...

Страница 46: ...ON OFF 208 ON ON ON ON OFF ON OFF OFF 251 N O T U S E D 166 ON OFF OFF ON ON OFF ON OFF 209 OFF ON ON ON OFF ON OFF OFF 252 N O T U S E D 167 OFF OFF OFF ON ON OFF ON OFF 210 ON OFF ON ON OFF ON OFF...

Страница 47: ...m voltage Multi Relay Module RM NO N A Isolated from system voltage Multi Relay Module RM CM N A Isolated from system voltage Multi Relay Module RM NC N A Isolated from system voltage In quiescent con...

Страница 48: ...m 48 Installation Manual Modification History Issue Date Changes 001 19 03 2020 Added manual modification history table Impedance values changed to 10K Removed non LED MMP10 MMP26 version Changed PSU...

Отзывы: