SCM-ZMM Field Wiring Connections
Wiring Recommendations for Zone Monitor Circuits
(SCM-ZMM)
Wire Gauge (AWG)
Maximum Wiring Run (Metres)
22
910
20
1450
18
2300
SCM-ZMM Specifications
Zone Monitor Modules (SCM-ZMM)
Circuit Voltage
26VDC Nominal (17.5V - 26.5V with EOL connected)
Circuit Type
Power limited & Supervised
Wiring Class
Class B
Zone Maximum Line Impedance
10Ω
Zone Maximum Current (under S/C conditions)
56mA
Wiring Class
6 x Class B circuits
Recommended cable sizes
22 AWG to 14 AWG (0.3mm
2
to 2.5mm
2
)
End of Line Resistor
4K7Ω
Alarm Trigger Resistor
1
KΩ
Compatible Devices
MKII-OP, MKII-HR, MKII-HF, MKII-HF-CS90, MKII-OH, ZT-CP3
(All are EN54
approved)
Maximum Detectors Per Zone
20
RECOMMENDED CABLE:
Cable should be BS approved FPL, FPLR, FPLP or equivalent.
While SMART Connect Multi-loop conventional Zone modules can
support cable runs greater than 2000m, it is generally better to plan
the system to use more manageable lengths.
NOTE:
It is not recommended to mix
different detector manufacturers on
a zone.
NOTE:
It is recommended that all
manual call points are connected at
the start of the zone.