Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
30
SCM-LCM Field Wiring Connections
Class X Wiring
Class A Wiring
Note:
If a loop using Class A wiring is used for 2 or more detection zones, short circuit
isolators, or devices with built in short circuit isolators (such as interfaces) should be
fitted to the zone boundaries to prevent a single short circuit affecting more than one
zone.
Note:
Detectors can be fitted to isolator bases, or fitted between isolator modules for
Class X wiring. Manual stations should be fitted between isolator modules.