PREMIER POWER PACK INSTRUCTION MANUAL
GLT.MAN-138
PAGE 4
Issue: 1.13 27/7/2012 N.R.P.J.
INDICATIONS
LCD
The Stand alone Premier Power Pack PSU has a 4 line LCD display, which can show the current state of the power
supply.
The Power supply has 2 buttons. The first turns on the backlight. The second will scroll through the available
display screens, showing the PSU`s current state.
Screen 1: PSU Model information and System Normal / Power Supply Fault Indication
Z E T A
A L A R M
S Y S T E M S
P R E M I E R
P O W E R - P A C K
R A T I N G
3 0 V
D C
5 . 6 A
S Y S T E M
N O R M A L
This is the model information screen. It will give a general indication of the system state in the bottom line.
System Normal for a healthy system. Power Supply Fault if there are any problems.
Screen 2: Mains / Battery Healthy, PSU output Voltage, PSU output current
M A I N S :
O K
B A T T S :
O
K
V ( A ) = 2 9 . 5
V ( B ) = 2 9 .
5
V
C U R R E N T
0 . 1 2
A M P S
This screen shows whether mains and battery are OK or BAD. It also shows the output voltage, and the current
being supplied. In the event of a blown 24V output fuse, the screen will show V(A)=BAD or V(B)=BAD.
Screen 3: Battery Charger Info
B A T T E R Y
I M P : 0 . 0 0 3 7
C H A R G E R
V O L T : 2 5 . 4 5 V
C H A R G E
T Y P E :
B O O S T
B A T T E R Y
S T A T E : G O O D
This screen gives information about the battery & charger circuit. The Battery IMP(edance) is the internal
resistance of the battery , explained in the recent changes to EN 54-4 section.
The Charger Voltage will be the voltage at the battery terminals.
The Charge Type gives the current charging method. The methods used are:-
BOOST – Constant current charge of 920mA. Used when batteries are flat
FLOAT
– Float charge is applied as the batteries approach a full charge
PULSE
– used when the voltage at the charger terminals is less than the final voltage. Used to check if the
batteries are present.
OFF
– Charger is turned off when no mains is present