PREMIER POWER PACK INSTRUCTION MANUAL
GLT.MAN-138
PAGE 13
Issue: 1.13 27/7/2012 N.R.P.J.
TECHNICAL INFORMATION
OVERALL SPECIFICATION
5.0 A PSU
2.0 A PSU
MAINS INPUT
Nominal Mains Supply Voltage
230V AC
230V AC
Cage Input voltage range
88
~
132 VAC / 176
~
264 VAC
47
~
63 Hz
;
88
~
264 VAC
47
~
63 Hz
;
AC input current
2.4 A/115 V 1.6A/ 230 V
2.0A/115 V 1.2A/ 230 V
Efficiency
86%
85%
AC inrush current
Cold starting current 45A/230VAC Cold starting current 40A/230VAC
Leakage current
<
2 mA/240VAC
<
2mA/240VAC
SWITCH MODE CAGE OUTPUT
Nominal DC Output voltage
30V
30V
Output Voltage Error
+/- 1%
+/- 1%
Output Power
150W
75W
Rated output current @ 30V DC
5 A
2.5 A
Adjustable range for DC voltage
27 – 30.6V
27 – 33V
Setup rise hold up time
800ms,20ms,24ms, Full-load
500ms,30ms,60ms Full-load
PSU OUTPUT
Nominal DC Output voltage
30V
30V
Output Voltage Range
19 – 31 V DC
19 – 31 V DC
Maximum PSU output while charging
I MAX A
4.1A
1.4A
I MAX B
N/A
N/A
I MIN
0 mA
0mA
Output Fuses
2 x 2.5A
2 x 1.0A
Output Voltage Ripple
Typical 120mVp-p (Max 500mV)
Typical 150mVp-p (Max 500mV)
Fault Output
Normally Energised Volt-Free
Change over Relay: SELV @ 1A
Normally Energised Volt-Free
Change over Relay: SELV @ 1A
BATTERY BACKUP
Battery type
2 x 12V Sealed Lead Acid
Batteries connected in SERIES
2 x 12V Sealed Lead Acid
Batteries connected in SERIES
Battery Size Range
7.0 – 17 Ah
2.0 – 12 Ah
Charger Type
CPU controlled 3 state charger
(boost, float, pulse modes)
CPU controlled 3 state charger
(boost, float, pulse modes)
Boost Charging current
920mA
750mA
Float Charging current
200mA Typical
200mA Typical
Pulse charging
10% duty cycle
10% duty cycle
Battery fuse
5A (in battery link lead)
5A (in battery link lead)
Maximum battery internal resistance
0.9 ohm
2.0 ohm
Battery Deep Discharge Disconnect
20.5 Volts At battery (19V at PSU
output)
20.5 Volts At battery (19V at PSU
output)
Deep Discharge Reconnection
When mains restored
When mains restored
Charger Temp. Compensation
-36mV/
o
C typical (27-46 mV/
o
C)
-36mV/
o
C typical (27-46 mV/
o
C)
PSU Battery Drain – in Mains Fail
25mA (40 mA with LCD Screen)
25mA (40 mA with LCD Screen)
Max Battery Monitoring Current (R int test)
460mA
460mA
LED INDICATIONS (PSE and CIE Version)
GREEN Power
Steady = Mains OK
Flashing = Mains Fail
Steady = Mains OK
Flashing = Mains Fail
General Fault
Flashes on Mains Fail or Output
voltage failure
Flashes on Mains Fail or Output
voltage failure
Earth Fault
Flashes on +VE or –VE earth fault
(if enabled)
Flashes on +VE or –VE earth fault
(if enabled)
Battery Fault
Flashes on any battery fault.
Flashes on any battery fault.