It is possible to use a mixture of DMX and iCANnet control inputs to control RigSwitch.
The three control options are CAN only, DMX only and DMX if Present, which can be configured per channel. These
are described as follows:
When in CAN only mode, DMX input is ignored.
When in DMX only mode, CAN is ignored.
When in DMX If Present mode, DMX can take control of a channel, if the DMX level for that channel is taken up
to match the current level currently controlled by CAN. DMX then takes control of the channel. DMX will remain
in control of that channel until the DMX signal is lost.
If an Alarm input, or Alarm CAN message is received, this will override the DMX input.
If controlling with DALI and the SCMR1232 in RigSwitch is configured as a DALI end device, iCANnet and DMX
control will be ignored.
Alarm Input
RigSwitch cabinets include an SCMR1232 relay controller, which feature close-contact terminals. RigSwitch 12 include
one SCMR1232, and RigSwitch 24 include two.
The pair of close contact terminals, marked IN1 and IN2, share a common terminal. They can be configured as an
Alarm input. When configured as an alarm, by default when an alarm input is received all channels will be switched on.
This can however be configured.