Illustrations - Refrigeration Line Sizing - Frozen Foods • 37
ILLUSTRATIONS
FIGURE 20
Refrigeration Line Sizing - Frozen Foods
40°F
50°F
60°F
70°F
80°F
90°F
100°F
120°F
0.96
0.95
0.95
0.95
0.97
1.00
1.05
1.21
Liquid Correction Factor:
110°F
1.12
Liquid Correction Factors for Liquid Line Sizing Table - Use Maximum Liquid Temperature
For maximum liquid temperatures other than 90°F, multiply rated Btuh by liquid correction factor before using the Liquid Line Sizing Table
Maximum Liquid Temperature:
Suction Horizontal Line Sizing
Up to 50 equivalent feet
Up to 100 equivalent feet
Up to 150 equivalent feet
Up to 200 equivalent feet
90°F Liquid, 2°F Pressure Drop
‡
90°F Liquid, 2°F Pressure Drop
‡
90°F Liquid, 2°F Pressure Drop
‡
90°F Liquid, 2°F Pressure Drop
‡
From
To
Horizontal
From
To
Horizontal
From
To
Horizontal
From
To
Horizontal
0
1,730
3/8
++
0
1,180
3/8
++
0
940
3/8
++
0
800
3/8
++
1,740
4,100
1/2
++
1,190
2,810
1/2
++
950
2,240
1/2
++
810
1,910
1/2
++
4,110
7,700
5/8
++
2,820
5,280
5/8
++
2,250
4,220
5/8
++
1,920
3,600
5/8
++
7,710 12,800
7/8
†
5,290
8,780
7/8
†
4,230
7,030
7/8
†
3,610
6,000
7/8
†
12,810 20,300
7/8
8,790 14,000
7/8
7,040 11,200
7/8
6,010
9,530
7/8
20,310 41,000
1-1/8
14,010 28,200
1-1/8
11,210 22,700
1-1/8
9,540 19,400
1-1/8
41,010 71,400
1-3/8
28,210 49,200
1-3/8
22,710 39,500
1-3/8
19,410 33,800
1-3/8
71,410 113,000
1-5/8
49,210 77,800
1-5/8
39,510 62,500
1-5/8
33,810 53,500
1-5/8
62,510 130,000
2-1/8
53,510 112,000
2-1/8
‡
For 1°F pressure drop, multiply rated BTU by 1.44 before using the Suction Horizontal Line Sizing Table.
++
Larger suction horizontal line size may be used, if preferred.
†
3/4 horizontal suction line may be used to reduce cost.
For rated Btuh:
For rated Btuh:
For rated Btuh:
For rated Btuh:
40°F
50°F
60°F
70°F
80°F
90°F
100°F
120°F
0.72
0.76
0.81
0.86
0.92
1.00
1.09
1.37
Liquid Correction Factors for Suction Horizontal Line Sizing Table - Use Maximum Liquid Temperature
For maximum liquid temperatures other than 90°F, multiply rated Btuh by liquid correction factor before using the Suction Horizontal Line Sizing Table
Maximum Liquid Temperature:
Liquid Correction Factor:
1.21
110°F
Suction Vertical Riser Sizing
Maximum Allowable Riser Size For Adequate Oil Return*
70°F Minimum Liquid Temperature, using 0.35 PSI Per 100 Feet (per 2006 ASHRAE Handbook - Refrigeration).
For rated Btuh:
From
To
Vertical
1,360
2,550
1/2
2,560
4,270
5/8
4,280
6,790
5/8
†
6,800 13,900
7/8
13,910 24,300
1-1/8
24,310 38,400
1-3/8
38,410 80,000
1-5/8
80,010 142,000
2-1/8
* If horizontal line size is smaller than specified vertical riser size, the smaller size may be used for both.
†
3/4 suction riser may be used to reduce pressure drop.
It may be necessary to make adjustments to compensate for
special situations which cause the actual Btuh to differ from
the rated Btuh of the cases.
All liquid line and suction line sizes are inches, refrigeration O.D.
Subject to change without notice.
R-404 Line Sizing Tables for Zero Zone VZ/VLC Frozen Food Freezer (-7°F Evaporator Temperature)
Liquid Line Sizing - Electric Defrost*
Up to 50 equivalent feet
Up to 100 equivalent feet
Up to 150 equivalent feet
Up to 200 equivalent feet
90°F Liquid, 2°F Pressure Drop
?
90°F Liquid, 2°F Pressure Drop
?
90°F Liquid, 2°F Pressure Drop
?
90°F Liquid, 2°F Pressure Drop
?
From
To
Liquid Line
From
To
Liquid Line
From
To
Liquid Line
From
To
Liquid Line
0
7,300
1/4
+
0
4,970
1/4
+
0
3,960
1/4
+
0
3,370
1/4
+
7,310 15,000
5/16
+
4,980 10,300
5/16
+
3,970
8,150
5/16
+
3,380
6,940
5/16
+
15,010 27,300
3/8
10,310 18,700
3/8
8,160 14,900
3/8
6,950 12,700
3/8
27,310 64,600
1/2
18,710 44,300
1/2
14,910 35,500
1/2
12,710 30,300
1/2
64,610 122,000
5/8
44,310 83,200
5/8
35,510 66,700
5/8
30,310 56,900
5/8
* For hot gas defrost, use a liquid line one size larger than shown.
66,710 111,000
7/8
†
56,910 94,800
7/8
†
?
For 1°F pressure drop, multiply rated Btuh by 1.45 before using the Liquid Line Sizing Table.
+
Larger liquid line size may be used (such as 3/8), if preferred.
†
3/4 liquid line may be used to reduce cost.
For rated Btuh:
For rated Btuh:
For rated Btuh:
For rated Btuh:
Liquid Correction Factors for Suction Vertical Riser Sizing Table - Use Minimum Liquid Temperature
Multiply rated Btuh by liquid correction factor before using the Suction Vertical Riser Sizing Table
40°F
50°F
60°F
70°F
80°F
90°F
100°F
0.84
0.88
0.94
1.00
1.07
1.16
1.27
Minimum Liquid Temperature:
Liquid Correction Factor:
PES, 2/1/16
SP-0612-01, Rev C
Содержание RVLC30
Страница 23: ...Illustrations RVLC30 Base Locations 21 Illustrations Figure 4 RVLC30 Base Locations Refer back to page 5 ...
Страница 24: ...22 Illustrations RVLC30BB Base Locations Illustrations Figure 5 RVLC30BB Base Locations Refer back to page 5 ...
Страница 25: ...Illustrations Case Squareness 23 Illustrations Figure 6 Case Squareness Refer back to page 5 ...
Страница 26: ...24 Illustrations Shim Placement Illustrations Figure 7 Shim Placement Refer back to page 5 ...
Страница 27: ...Illustrations Shim Orientation 25 Illustrations Figure 8 Shim Orientation Refer back to page 5 ...
Страница 29: ...Illustrations Spacer Block 27 Illustrations Figure 10 Spacer Block Refer back to page 6 ...
Страница 34: ...32 Illustrations Drain Line Illustrations Figure 15 Drain Line Refer back to page 7 ...
Страница 38: ...36 Illustrations Electrical Box Illustrations Figure 19 Electrical Box Refer back to page 11 ...