The Carel controller has a two-level menu system for programming the operation of the case. Level 1 program settings are the most frequently 

accessed parameters. These items are used to make simple changes to the operation of the case. Level 2 program settings control more 

complicated aspects of the case operation and, therefore, require the use of a password to gain access.

HOW TO CHANGE LEVEL 1 CONTROL SETTINGS

1.  Press and hold the Program [Prg] button down for 5 seconds. “St” will be shown on the display.
2.  Use the [Up] and [Down] arrows to move up or down the menu until you reach the parameter you intend to view or change. When the 

proper code is displayed, press the [Set] button to view the current setting for that parameter.

3.  Use the [Up] and [Down] arrows to change the value. Then press the [Set] button again to return to the menu.
4.  The only exception to Step #3 is the real time clock, program code “tc”. In this case, you must press the [Set] button in order to access the 

submenu of available settings for the “tc”parameter. Then press the [Up] and [Down] arrows to move up and down the submenu. Once 

changes are made in this submenu, press the [Prg] button to get back to the main menu.

5.  When finished making all necessary changes, you MUST press and hold the [Prg] button for 10 seconds to save them. Alternatively, if 

you decide you do NOT want to save changes you’ve just made, simply stop pressing buttons for 30 seconds and the control will return to 

normal operation, discarding any changes made.

HOW TO CHANGE LEVEL 2 CONTROL SETTINGS

6.  Press and hold the [Prg] and [Set] buttons down for 5 seconds. The display will show a flashing “0”.
7.  Use the [Up] arrow until the display reads “22” (this is the password), then press the [Set] button. The display will read “/P”.
8.  Use the [Up] and [Down] arrows to move up or down the menu until you reach the parameter you intend to view or change. When the 

proper code is displayed, press the [Set] button to view the current setting for that parameter. (You will notice the Level 1 program codes 

are also found in this menu.)

9.  Use the [Up] and [Down] arrows to change the value. Then press the [Set] button again to return to the menu.
10.  The exceptions to Step #4 are the program codes “tc”“td1”, and “td2”. In these cases, you must press the [Set] button in order to 

access the submenu of available settings for these parameters. Once changes are made in this submenu, press the [Prg] button to get 

back to the main menu.

11.  When finished making all necessary changes, you MUST press and hold the [Prg] button for 10 seconds to save them. Alternatively, if 

you decide you do NOT want to save changes you’ve just made, simply stop pressing buttons for 30 seconds and the control will return to 

normal operation, discarding any changes made.

Note: Zero Zone should be contacted before working on changing settings. To be completed by a trained person only.

ZERO ZONE, INC.  •  800-247-4496  •  ZERO-ZONE.COM 

© 2015 Zero Zone, Inc. All Rights Reserved.  •  MAR 2015

MN-06-B

CAREL CONTROLLER

Programming Instructions

Содержание Carel

Страница 1: ...buttons for 30 seconds and the control will return to normal operation discarding any changes made HOW TO CHANGE LEVEL 2 CONTROL SETTINGS 6 Press and hold the Prg and Set buttons down for 5 seconds Th...

Страница 2: ...VEL 2 Code Name Factory Set A2 Probe 2 con guration 2 c1 Min time between starts 5 c2 Min comp OFF 1 c3 Min comp ON 1 d0 Defrost type 4 dd Drip time 1 dn Defrost duration 100 AL Low temp alarm 20 AH H...

Страница 3: ...f month tc u RTC day of week tc h RTC hour tc m RTC minute MEDIUM TEMP LEVEL 2 Code Name Factory Set A2 Probe 2 con guration 0 c1 Min time between starts 5 c2 Min comp OFF 1 c3 Min comp ON 1 d0 Defros...

Страница 4: ...erations 1 The case s condensing unit mounted on top of the case cycles off and on during normal operation When the inside of the case is warm the compressor turns on When the inside of the case is co...

Страница 5: ...for the electronic control can be found affixed to the ceiling of each case inside the right hand door See Manager s Emergency Guide at the end of this manual The button used to silence the alarm Prg...

Страница 6: ...er will reset If the case is in defrost the electronic display will read DEF Common Things to Check DEFROST AND ALARMS 1 Check the circuit breakers for the cases Tripped circuit breakers will cut off...

Страница 7: ...se was not recently stocked with product Holding one of the doors open for an extended period of time as is the case when stocking will raise the internal temperature and possibly set off the alarm c...

Отзывы: