ZoningBOX 6 / ZoningBOX 4
Technical Support:
34
Initial Position
[
No Change
/ Open / Close / Position
]: sets the action to be
performed by the grille after the start-up of the device.
If “Position” is selected,
exclusive for
positional mode
, the following parameter will be displayed:
➢
Initial Position Value
[
0…
50
…100 %
]: grille desired position at
initialization.
Advance Current Control
[
disabled
/enabled
]: it enables the option of set an
advance current control. If it is enables, the follow parameter will be show:
➢
Current Increment for Cut-Off
[
25…
120
…150 mA
]: increase over the
nominal value of the current that should determine the end of the
movement of the grid.
Important: Its use is not recommended except for exceptional cases where
advanced control of the ZoningBOX is necessary
.
2.3.3
ERROR NOTIFICATION
Enabling the error notification function allows ZoningBOX to report certain error events
through the KNX bus:
Connection error
: it will be reported when either an open circuit or a short-
circuit is detected in an output (i.e., in the grille wiring). When this happens,
ZoningBOX interrupts the power supply to the output. The persistence of the
error will be checked whenever a new request to operate the grille is
received.
Overload
: this error is reported in case ZoningBOX detects the current
demand is higher than expected during the synchronisation process (see
section 2.3), which happens when more than two grilles are wired to the
same output. Although the output will still respond to any position change
requests, issues may be expected during the grille motion.
Maximum Safety Time
: this error takes place in case ZoningBOX considers
the grille is taking too much time to complete motion, i.e., to reach the end-of-
stroke position. In such case, the grille will be stopped.