LUMENTO X4
LED DIMMING
RGB CONTROLLER
ZN1DI-RGBX4
Technical Documentation
© Zennio Avance y Tecnología S.L. Edition 4 For further information
www.zennio.com
Page.
1
of
2
FEATURES
Control of RGBW LED or 4 independent channels.
External power supply required (12 or 24 VDC).
LED test function.
Integrated KNX BCU.
Conformity with the CE directives.
1.
KNX
connector
2.
KNX programming and
internal test LED
3.
KNX programming
button
4.
Test button
5.
LED control
terminal block
6.
External
power supply
7.
Test and reversed
polarity indicator LED
GENERAL SPECIFICATIONS
Type of device
Electric operation control device
KNX supply
Voltage (typical)
29VDC
Voltage range
21
…31VDC
Power consumption
145mW
Connection type
Typical bus connector TP1, 0.80mm2 section
External power supply
12 or 24VDC
Power supply cable section
1.5 mm² to 2.5 mm²
Type of control
PWM (150, 300, 488 or 600 Hz)
Operation temperature
0ºC to +45ºC
Storage temperature
-5ºC to +50ºC
Operation humidity
30 to 85% RH (no condensation)
Storage humidity
30 to 85% RH (no condensation)
Complementary characteristics
Class B
Protection class
II
Operation type
Continuous operation
Device action type
Type 1
Electrical stress period
Long
Protection degree
IP20, clean environment
Installation
Surface mounted independent device
Connect LUMENTO as near as possible to both, the LED to dimmer and the external power supply
Response on KNX bus failure
Data saving
Response on KNX bus restart
Data recovery
PCB CTI index
175V
Housing material
PC-ABS FR V0 halogen free
Dimensions
Without terminal blocks: 144x44x22mm / With terminal blocks: 157x44x22mm
Weight
104g
Operation indication
Programming/internal test LED indicates: programming mode (red lighting), safe mode (red
blinking) and internal test (blue blinking).
Test LED indicates: white, test channel 4 (W); red, test channel 1 (R); green, test channel 2 (G);
blue, test channel 3 (B). Reverse polarity of external power supply is indicated by the test LED with
orange light.
KNX programming button:
short button press to set the programming mode. If this button is held while plugging the device to
the KNX bus, it enters into safe mode.
KNX programming and internal test LED:
the red LED indicates programming mode. When the device goes into safe mode, it
blinks red every 0.5 seconds. The blinking blue LED indicates internal test.
Test button
: it tests the functioning of channels connected to the device. Push and hold for 3 seconds to get in/out of the testing
mode.
Test LED and polarity:
tricolored LED that indicates which channel (red=channel 1/R, green=channel 2/G, blue=channel 3/B,
qhite=channel 4/W) is being tested. Orange light indicates reverse polarity in external power supply.
3
3
4
5
7
2
1
6
Figure 1.
LUMENTO X4