ANNEX I. COMMUNICATION OBJECTS 

 

“Functional range

” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a 

particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself. 

Note

objects referring to inputs and thermostats only apply to inBOX 24

Name

 

Size

 

I/O

 

Flags

 

Data Type (DPT)

 

Functional Range

 

Name

 

Function

 

1

 

1 Bit

 

 

C T - - -

 

DPT_Trigger

 

0/1

 

[Heartbeat] Object to Send '1'

 

Sending of '1' Periodically

 

2

 

1 Bit

 

 

C T - - -

 

DPT_Trigger

 

0/1

 

Reset 0

 

Voltage Recovery -> Sending 0

 

3

 

1 Bit

 

 

C T - - -

 

DPT_Trigger

 

0/1

 

Reset 1

 

Voltage Recovery -> Sending 1

 

4

 

1 Bit

 

I

 

C - - W -

 

DPT_Switch

 

0/1

 

Manual Control Lock

 

0 = Lock; 1 = Unlock

 

1 Bit

 

I

 

C - - W -

 

DPT_Switch

 

0/1

 

Manual Control Lock

 

0 = Unlock; 1 = Lock

 

5 - 36

 

1 Bit

 

I

 

C - - W -

 

DPT_Bool

 

0/1

 

[LF] (1 bit) Data Entry x

 

Binary Data Entry (0/1)

 

37 - 52

 

1 Byte

 

I

 

C - - W -

 

DPT_Value_1_Ucount

 

0 - 255

 

[LF] (1 byte) Data Entry x

 

1 byte Data Entry (0-255)

 

53 - 68

 

2 Byte

 

I

 

C - - W -

 

DPT_Value_2_Ucount

 

0 - 65535

 

[LF] (2 bytes) Data Entry x

 

2 bytes Data Entry

 

DPT_Value_2_Count

 

-32768 - 32767

 

DPT_Value_Temp

 

-273.00 - 670760.00

 

69 - 76

 

4 Byte

 

I

 

C - - W -

 

DPT_Value_4_Count

 

-2147483648 - 

2147483647

 

[LF] (4 bytes) Data Entry x

 

4 bytes Data Entry

 

77 - 86

 

1 Bit

 

O

 

C T R - -

 

DPT_Bool

 

0/1

 

[LF] Function x - Result

 

(1 bit) Boolean

 

1 Byte

 

O

 

C T R - -

 

DPT_Value_1_Ucount

 

0 - 255

 

[LF] Function x - Result

 

(1 byte) Unsigned

 

2 Byte

 

O

 

C T R - -

 

DPT_Value_2_Ucount

 

0 - 65535

 

[LF] Function x - Result

 

(2 bytes) Unsigned

 

4 Byte

 

O

 

C T R - -

 

DPT_Value_4_Count

 

 

[LF] Function x - Result

 

(4 bytes) Signed

 

1 Byte

 

O

 

C T R - -

 

DPT_Scaling

 

0% - 100%

 

[LF] Function x - Result

 

(1 byte) Percentage

 

2 Byte

 

O

 

C T R - -

 

DPT_Value_2_Count

 

-32768 - 32767

 

[LF] Function x - Result

 

(2 bytes) Signed

 

2 Byte

 

O

 

C T R - -

 

DPT_Value_Temp

 

-273.00 - 670760.00

 

[LF] Function x - Result

 

(2 bytes) Float

 

87

 

1 Byte

 

I

 

C - - W -

 

DPT_SceneControl

 

0-63; 128-191

 

[Outputs] Scenes

 

0 – 63 (Execute 1 – 64); 128 – 191 (Save 1 – 64)

 

88

 

1 Bit

 

I

 

C - - W -

 

DPT_BinaryValue

 

0/1

 

[O1] On/Off

 

N.O. (0=Open Relay; 1=Close Relay)

 

1 Bit

 

I

 

C - - W -

 

DPT_BinaryValue

 

0/1

 

[O1] On/Off

 

N.C. (0=Close Relay; 1= Open Relay)

 

89

 

1 Bit

 

O

 

C T R - -

 

DPT_BinaryValue

 

0/1

 

[O1] On/Off (Status)

 

0=Output Off; 1=Output On

 

90

 

1 Bit

 

I

 

C - - W -

 

DPT_Enable

 

0/1

 

[O1] Lock

 

0=Unlock; 1=Lock

 

Содержание ZIO-IB24

Страница 1: ...inBOX 24 inBOX 20 Multifunction Actuator for Flush Mounting ZIO IB24 USER MANUAL ZIO IB20 Application program version 1 0 User manual edition 1 0 _a www zennio com...

Страница 2: ...nstallation 4 1 3 Start Up and Power Loss 5 2 Configuration 6 2 1 General 6 2 2 Inputs Only inBOX 24 8 2 2 1 Binary Input 8 2 2 2 Temperature Probe 9 2 2 3 Motion Detector 9 2 3 Outputs 10 2 3 1 Manua...

Страница 3: ...e 2 relay outputs configurable as 1 shutter channel with or without slats or Up to 2 individual ON OFF outputs 4 multi purpose inputs configurable as Temperature probes Binary inputs i e pushbuttons s...

Страница 4: ...ly analogous for inBOX 20 although the inputs are not available The main elements of the device are described next Test Prog Pushbutton 3 a short press on this button sets the device into the programm...

Страница 5: ...ce and also available at www zennio com 1 3 START UP AND POWER LOSS During the start up of the device the Test Prog LED will blink in blue colour for a few seconds before the device is ready External...

Страница 6: ...ate deactivate all the required functionality Figure 2 Default screen Once activated Inputs only in inBOX 24 Outputs Logic Functions Thermostats only in inBOX 24 Master Light Scene Temporisation and M...

Страница 7: ...It is possible to parameterise a certain delay to this sending 0 to 255 seconds Figure 3 Sending of Indication objects on bus voltage recovery Heartbeat Periodical Alive Notification this parameter l...

Страница 8: ...IO DETEC X from Zennio Important older models of the Zennio motion detector e g ZN1IO DETEC and ZN1IO DETEC N will not work properly with inBOX 24 ETS PARAMETERISATION When Inputs has been activated i...

Страница 9: ...r available in the inBOX 24 product section at the Zennio website www zennio com Notes The ZN1IO DETEC P motion detector is compatible with a variety of Zennio devices However depending on the device...

Страница 10: ...re available per output Manual operation can be done in two different ways named as Test On Mode for testing purposes during the configuration of the device and Test Off Mode for a normal use anytime...

Страница 11: ...he device will act over the output according to the length of the button press and to the current state A long press makes the shutter start moving upwards or downwards depending on the button being p...

Страница 12: ...position of the shutter and the parameterised times Note after leaving the Test On mode the status objects will recover the values they had prior to entering Test On As the device is never aware of t...

Страница 13: ...ecial action while switching to the Test On mode does require long pressing the Prog Test button Lock Manual Control unless the above parameter has been Disabled the Lock Manual Control parameter prov...

Страница 14: ...ution of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterisable communication objects The result after execu...

Страница 15: ...implements four Zennio thermostats which can be enabled and configured independently Please refer to the specific Zennio Thermostat user manual available in the inBOX 24 product section at the Zennio...

Страница 16: ...to the KNX bus in both cases a shutter order a thermostat setpoint or mode switch order a constant value a scene Only the trigger object and the twelve status objects are required to be binary on off...

Страница 17: ...takes off Scene if checked object ML General Switch off Scene will be enabled which will send a scene run save order configurable in Action and Scene Number whenever the general switch off takes off...

Страница 18: ...tp support zennio com 18 when the courtesy switch on takes place in contrast to object ML General Switch Off Binary Object which sends the value 0 during the general switch off as explained above Figu...

Страница 19: ...ing for that output or that channel such temporisation will be interrupted and only the delay and the action of the new scene will be executed ETS PARAMETERISATION Prior to setting the scene temporisa...

Страница 20: ...e scene temporisation Therefore parameter Scene m Z Delay defines the delay that will be applied to the action defined in Z for the execution of scene m where Z may be a specific individual output shu...

Страница 21: ...ta Entry x 1 byte Data Entry 0 255 53 68 2 Byte I C W DPT_Value_2_Ucount 0 65535 LF 2 bytes Data Entry x 2 bytes Data Entry DPT_Value_2_Count 32768 32767 DPT_Value_Temp 273 00 670760 00 69 76 4 Byte I...

Страница 22: ...105 1 Bit I C W DPT_UpDown 0 1 CA Move 0 Raise 1 Lower 106 1 Bit I C W DPT_Step 0 1 CA Stop Step 0 Stop StepUp 1 Stop StepDown 1 Bit I C W DPT_Trigger 0 1 CA Stop 0 Stop 1 Stop 107 1 Bit I C W DPT_Ena...

Страница 23: ...Door 0 1 Tx Window Status input 0 Closed 1 Open 132 162 192 222 1 Bit I C W DPT_Trigger 0 1 Tx Comfort Prolongation 0 Nothing 1 Timed Comfort 133 163 193 223 1 Byte O C T R DPT_HVACMode 1 Comfort 2 St...

Страница 24: ...us Object 5 Binary Status 249 1 Bit I C W DPT_Switch 0 1 ML Status Object 6 Binary Status 250 1 Bit I C W DPT_Switch 0 1 ML Status Object 7 Binary Status 251 1 Bit I C W DPT_Switch 0 1 ML Status Objec...

Страница 25: ...C T DPT_UpDown 0 1 Ix Short Press Move Up Down Shutter Switching 0 1 Up Down 1 Bit C T DPT_Step 0 1 Ix Short Press Stop Step Up Shutter Sending of 0 Stop Step Up 1 Bit C T DPT_Step 0 1 Ix Short Press...

Страница 26: ...rt Press Dimming Status Input 0 100 284 290 296 302 1 Bit C T DPT_Switch 0 1 Ix Long Press 0 Sending of 0 1 Bit C T DPT_Switch 0 1 Ix Long Press 1 Sending of 1 1 Bit I C T W DPT_Switch 0 1 Ix Long Pre...

Страница 27: ...1 Bit O C T R DPT_Alarm 0 1 Ix Open Circuit Error 0 No Error 1 Open Circuit Error 309 338 367 396 1 Bit O C T R DPT_Alarm 0 1 Ix Short Circuit Error 0 No Error 1 Short Circuit Error 310 339 368 397 1...

Страница 28: ...dby Economy Building Protection 328 357 386 415 1 Bit O C T R DPT_Switch 0 1 Ix C2 Detection State Binary Binary Value 329 358 387 416 1 Bit I C W DPT_Switch 0 1 Ix C2 Enable Channel According to para...

Страница 29: ...n and send us your inquiries about Zennio devices http support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio c...

Отзывы: