SAFETY INSTRUCTIONS AND ADDITIONAL NOTES 

 Installation should only be performed by qualified professionals according to the laws and regulations applicable in each cou ntry. 

 Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for the entire 

KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of other 
accessories, in case of being installed. 

 Once the device is installed (in the panel or box), it must not be accessible from outside. 

 Keep the device away from water (condensation over the device included) and do not cover it with clothes, paper or any other material 

while in use. 

 The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions at 

https://www.zennio.com/en/legal/weee-regulation. 

 This device contains software subject to specific licences. For details, please refer to https://zennio.com/licenses. 

OUTPUTS SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Number of outputs 

Output type / Disconnection type 

Potential-free outputs through bistable relays with 
tungsten pre-contact / Micro-disconnection 

Rated current per output 

AC 16(6) A @ 250 VAC (4000 VA) 
DC 7 A @ 30 VDC (210 W) 

Maximum load 
per output 

Resistive 

4000 W 

Inductive 

1500 VA 

Maximum inrush current 

800 A/200 

μs 

165 A/20 ms 

Connections in adjacent outputs  

Possibility of connecting different phases. It is not 
allowed  to  connect  power  supplies  of  different 
order, SELV with NO SELV, in the same block.  

Total maximum current in device 

40 A 

Short-circuit protection 

NO 

Overload protection 

NO 

Connection method 

Screw terminal block (0.5 Nm max.) 

Cable cross-section 

0.5-4 mm² (IEC) / 20-12 AWG (UL) 

Outputs per common 

Maximum response time 

10 ms 

Mechanical lifetime (min. cycles) 

3 000 000 

Electrical lifetime (min. cycles)

100000 @ 8 A / 25000 @ 16 A (VAC) 

¹ Lifetime values could change depending on the load type. 

 

INPUTS SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Number of inputs 

Inputs per common 

Operation voltage 

+3.3 VDC in the common 

Operation current 

1 mA @ 3.3 VDC (per input) 

Switching type 

Dry voltage contacts between input and common 

Connection method 

Screw terminal block (0.4 Nm max.) 

Cable cross-section 

0.5-2.5 mm² (IEC) / 26-12 AWG (UL) 

Maximum cable length 

30 m 

NTC probe length 

1.5 m (extensible up to 30 m) 

NTC accuracy (@ 25 °C) ² 

±0.5 °C 

Temperature resolution 

0.1 °C 

Maximum response time 

10 ms 

² For Zennio temperature probes. 

  In  order  to  ensure  the  expected  status  of  the 

relays, please check that the device is connected to 
the KNX bus before energizing the power circuit. 
 

WIRING DIAGRAMS 

A1

A2

B1

B2

I

II

III

L

N

Figure 2: Wiring example (from left to right, 

and up to down): 2 loads, 2 loads connected 

to different phases, shutter and fan coil 

* In case of using ZN1IO-DETEC-P sensor, its micro switch number 2 must be in 

Type B position. 

** Zennio temperature probe or any NTC with known resistance values at three points in the range [-55, 150 ºC]. 

INPUTS CONNECTION 

Any combination of the following accessories is allowed in the inputs: 

Zennio  temperature 
probe.

 

 

 

Up  to  two  motion  sensors 
can  be  plugged  into  the 
same  device  input  (parallel 
wiring)

 

 

 

Screw 

terminal 

for 

connecting  Zennio  motion 
sensors*

 

Temperature Probe**

 

Motion Sensor

 

 

 

Switch/Sensor/ 

Push button

 

 

 

C IN

C IN

C I

C IN

C IN

C IN

C I

C IN

C IN

C IN

C I

C IN

A1

A2

M

N

L

A1

A2

N

L

L1

L2

A1

A2

N

L1

L1

L2

L2

C IN

C IN

C I

C IN

Attaching MINiBOX 45 v3 to DIN rail: 

Removing MINiBOX 45 v3 from DIN rail:

 

A1

A2

M

N

L

A1

A2

N

L

L1

L2

A1

A2

N

L1

L1

L2

L2

C IN

C IN

C I

C IN

Commons  of  different  devices 
must not be connected together.

 

Отзывы: