background image

© Zennio Avance y Tecnología S.L. 

Edition 2 

Further information 

www.zennio.com

 

Page 1/2 

 

MINiBOX 45 v3 

Multifunction actuator with 4 outputs and 5 inputs with KNX Secure 

ZIOMN45V3 

TECHNICAL DOCUMENTATION 

 

FEATURES 

 

4 configurable outputs: fan coil, shutter channels (up to 2) and individual 
outputs (up to 4) 

 

Outputs suitable for capacitive loads, maximum 140 µF 

 

Supports KNX Data Secure 

 

5 analog/digital inputs 

 

Manual output operation with push button and LED status indicator 

 

10 logic functions 

 

Output timing 

 

4 thermostats 

 

Total data saving on KNX bus failure 

 

Integrated KNX BCU (TP1-256) 

 

Dimensions 67 x 90 x 36 mm (2 DIN units) 

 

DIN rail mounting according to IEC 60715 TH35, with fixing clamp 

 

Possibility of connecting different phases in adjacent outputs 

 

Conformity with the CE, UKCA, RCM directives (marks on the right side) 

 

 

 

1. Analog/Digital inputs 

2. Outputs 

3. Output status LED indicator 

4. Output control button 

5. Programming/test LED  

6. Programming/test button 

7. KNX Connector 

8. Fixing clamp 

A1

A2

M

N

L

A1

A2

N

L

L1

L2

A1

A2

N

L1

L1

L2

L2

C IN

C IN

C I

C IN

8

 

Figure 1: MINiBOX 45 v3 

Programming/Test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe 
mode. If this button is held for more than 3 seconds, the device enters the test mode. In order to perform a KNX Secure factory reset, while the device 
is in safe mode, press the button for 10 seconds until the programming LED changes its state. 
 
Programming/Test LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The test mode is 
indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it starts a blue blinking sequence. 

GENERAL SPECIFICATIONS 

CONCEPT 

DESCRIPTION 

Type of device 

Electric operation control device 

KNX supply 

Voltage (typical) 

29 VDC SELV 

Voltage range 

21-31 VDC 

Maximum 
consumption 

Voltage 

mA 

mW 

29 VDC (typical) 

4.9 

142.1 

24 VDC¹ 

10 

240 

Connection type 

Typical TP1 bus connector for 0.8 mm Ø rigid cable 

External power supply 

Not required 

Operation temperature 

0 .. +55 °C 

Storage temperature 

-20 .. +55 °C 

Operation humidity 

5 .. 95% 

Storage humidity 

5 .. 95% 

Complementary characteristics 

Class B 

Protection class / Overvoltage category 

II / III (4000 V) 

Operation type 

Continuous operation 

Device action type 

Type 1 

Electrical stress period 

Long 

Degree of protection / Pollution degree 

IP20 / 2 (clean environment) 

Installation 

Independent device to be mounted inside electrical panels with DIN rail (IEC 
60715) 

Minimum clearances 

Not required 

Response on KNX bus failure 

Data saving according to parameterization 

Response on KNX bus restart 

Data recovery according to parameterization 

Operation indicator 

The programming LED indicates programming mode (red) and test mode 
(green). Each output LED indicates its status 

Weight 

148 g 

PCB CTI index 

175 V 

Housing material / Ball pressure test temperature 

PC FR V0 halogen free / 75 °C (housing) - 125 °C (connectors) 

¹ Maximum consumption in the worst-case scenario (KNX Fan-In model). 

Отзывы: