ANNEX I. COMMUNICATION OBJECTS
“Functional range
” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning
because of the specifications or restrictions from both the KNX standard or the application program itself.
Number
Size I/O Flags
Data type (DPT)
Functional Range
Name
Function
1
1 Bit
C T - - -
DPT_Trigger
0/1
Reset 0
Voltage Recovery -> Sending of 0
2
1 Bit
C T - - -
DPT_Trigger
0/1
Reset 1
Voltage Recovery -> Sending of 1
3
1 Bit
E
C - - W -
DPT_Switch
0/1
Manual Control Lock
0 = Lock; 1 = Unlock
1 Bit
E
C - - W -
DPT_Switch
0/1
Manual Control Lock
0 = Unlock; 1 = Lock
4
1 Byte
E
C - - W -
DPT_SceneControl
0-63; 128-191
[Thermostat] Scene Input
Scene Value
5, 35, 65, 95
2 Bytes
E
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Temperature Source 1
External Sensor Temperature
6, 36, 66, 96
2 Bytes
E
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Temperature Source 2
External Sensor Temperature
7, 37, 67, 97
2 Bytes
S
C T R - -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Effective Temperature
Effective Control Temperature
8,38, 68, 98
1 Byte
E
C - - W -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building Protection
[Tx] Special Mode
1-byte HVAC Mode
9, 39, 69, 99
1 Bit
E
C - - W -
DPT_Trigger
0/1
[Tx] Special Mode: comfort
0 = Nothing; 1 = Trigger
1 Bit
E
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: comfort
0 = Off; 1 = On
10, 40, 70, 100
1 Bit
E
C - - W -
DPT_Trigger
0/1
[Tx] Special Mode: standby
0 = Nothing; 1 = Trigger
1 Bit
E
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: standby
0 = Off; 1 = On
11, 41, 71, 101
1 Bit
E
C - - W -
DPT_Trigger
0/1
[Tx] Special Mode: economy
0 = Nothing; 1 = Trigger
1 Bit
E
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: economy
0 = Off; 1 = On
12, 42, 72, 102
1 Bit
E
C - - W -
DPT_Trigger
0/1
[Tx] Special Mode: protection
0 = Nothing; 1 = Trigger
1 Bit
E
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: protection
0 = Off; 1 = On
13, 43, 73, 103
1 Bit
E
C - - W -
DPT_Window_Door
0/1
[Tx] Window Status (input)
0 = Closed; 1 = Open
14, 44, 74, 104
1 Bit
E
C - - W -
DPT_Trigger
0/1
[Tx] Comfort Prolongation
0 = Nothing; 1 = Timed Comfort
15, 45, 75, 105
1 Byte
S
C T R - -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building Protection
[Tx] Special Mode Status
1-byte HVAC Mode
16, 46, 76, 106
2 Bytes
E
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Setpoint
Thermostat Setpoint Input