LUMENTO X4
LED DIMMING
RGB CONTROLLER
ZN1DI-RGBX4
Technical Documentation
© Zennio Avance y Tecnología S.L. Edition 3 For further information
www.zennio.com
Page.
1
of
2
FEATURES
Control of RGBW LED or 4 independent channels.
External power supply required (12 or 24 VDC).
LED test function.
KNX BCU integrated.
CE directive compliant.
1.
KNX
connector
2.
KNX programming and
internal test LED
3.
KNX programming
button
4.
Test button
5.
LED control
terminal block
6.
External
power supply
7.
Test and reversed
polarity indicator LED
GENERAL SYSTEM SPECIFICATIONS
Type of device
Electric operation control device
KNX supply
Voltage
29V DC típicos
Voltage range
21
…31V DC
Power consumption
145 mW
Bus connection
Typical BUS connector TP1, 0.50mm2 section
External power supply
12 or 24V DC
Power supply cable section
1.5 mm² to 2.5 mm²
Type of control
PWM (150, 300, 488 or 600 Hz)
Ambient temperature
0ºC to +45ºC
Storage temperature
-5ºC to +50ºC
Ambient humidity
30 to 85% RH (no condensation)
Storage humidity (relative)
30 to 85% RH (no condensation)
Complementary characteristics
Class B
Safety class
II
Operation type
Continuous operation
Device action type
Type 1
Electrical solicitations period
Long
Protection class
IP20, clean environment
Assembly
Independent control assembly device
Connect LUMENTO as near as possible to both, the LED to dimmer and the external power supply
Bus power failure response
Data saving
Response when restarting bus
Data recovery
PCB CTI index
175 V
Enclosure
PC-ABS FR V0 halogen free
Size
Without terminal blocks: 144x44x22mm / With terminal blocks: 157x44x22mm
Weight
102 g.
Operation indication
Programming/internal test LED indicates: programming mode (red lighting), safe mode (red
blinking) and internal test (blue blinking).
Test LED indicates: white, test channel 4 (W); red, test channel 1 (R); green, test channel 2 (G);
blue, test channel 3 (B). Reverse polarity of external power supply is indicated by the test LED with
orange light.
KNX programming button:
short button press to set the programming mode. If this button is held while plugging the device into
the KNX bus, it goes into safe mode.
KNX programming and internal test LED:
the red LED indicates programming mode. When the device goes into safe mode, it
blinks red every 0.5 seconds. The blinking blue LED indicates internal test.
Test button
: it tests the functioning of channels connected to the device. Push and hold for 3 seconds to get in/out of the testing
mode.
Test LED and polarity:
tricolored LED that indicates which channel (red=channel 1/R, green=channel 2/G, blue=channel 3/B,
qhite=channel 4/W) is being tested. Orange light indicates reverse polarity in external power supply.
3
3
4
5
7
2
1
6
Figure 1.
LUMENTO X4