Technical Documentation
© Zennio Avance y Tecnología S.L. Edition 4 Further information
Page
1
/
2
KCI
KNX Consumption Interface
ZRX-KCI4SO
Technical Documentation
FEATURES
4 channels for consumption counters (meters) with S0-pulse
outputs (UNE-EN 62053-31)
*
.
Registration of consumed electric power, cost and CO
2
emissions
that can be split in up to 4 time intervals.
Compliant with UNE-EN 62053-31 Class B.
Total data saving on KNX bus power failure.
KNX BCU integrated.
Size 90 x 60 x 35 mm (2 DIN units).
DIN rail unit assembly (EN 50022), with snap fit clamp.
CE directives compliant.
Programming button
: short button press to set the programming mode. If this button is held while plugging the device into the KNX bus, it goes into
safe mode.
Programming LED:
programming mode indicator (red). When the device goes into safe mode, it blinks (red) every half second.
LOW batt. LED
: if this LED is blinking in red, replace the batteries as soon as possible.
EMPTY batt. LED
: if this LED is blinking in red, the batteries are empty.
Figure 1:
KNX Consumption Interface
1.
Battery holder
2.
EMPTY batt. LED indicator
3.
LOW batt. LED indicator
4.
Programming button
5.
Programming LED
6.
Input Indicator LED
7.
Input connectors
8.
KNX connector
GENERAL SYSTEM SPECIFICATIONS
Concept
Description
Type of device
Electric operation control device
KNX
Supply
Voltage
29VDC SELV
Voltage range
21…31VDC
Max
consumption
Voltage
mA
mW
29VDC (typical)
12.5
363
24VDC
(1)
15
360
Bus connection
Typical bus connector TP1; 0.80mm² section
Battery (auxiliary power supply)
2 CR2032 battery (2 x 3V). It allows to keep counting pulses without the KNX bus
power supply
Working temperature
from 0ºC to +45ºC
Storage temperature
from -20ºC to +70ºC
Ambient humidity (relative)
30% to 85% RH (no condensation)
Storage humidity (relative)
30% to 85% RH (no condensation)
Complementary characteristics
Class B
Safety class
III
Operation type
Continuous operation
Device action type
Type 1
Electrical stress period
Long
Degree of protection
IP20, clean environment
Assembly
Independent device to be mounted inside electrical panels with DIN rail (EN 50022)
Minimum clearances
Not required
KNX bus failure response
Data saving according to parameterization
Response when restarting KNX bus
Data recovering according to parameterization
Operation indication
Programming LED indicates programming mode (red) or safe mode (blinking red).
LOW and EMPTY batt. LED indicate the battery level when blinking in red (KNX
supply necessary). LED input indicator blinks when a pulse is received
Weight
95g including batteries (89g without batteries)
PCB CTI index
175V
Housing material
PC FR V0 halogen free
(1)
Maximum consumption in the worst case scenario (KNX Fan-In model)
1
2
3
4
5
6
7
8
*Other counters (meters) with dry-voltage output or not complying S0 standard
may also work (previous test is recommended)