background image

 

 

 

                   IRSC Plus

 

http://www.zennio.com

 

                 

Technical Support:

 

http://support.zennio.com

 

 

21 

3.9

 

PRESENCE DETECTOR 

Presence  detectors  (like  Zennio’s 

ZN1IO-DETEC

  sensor),  installed  inside  a  room, 

permit  multiple  applications,  such  as  switching  lights  on  and  off,  detecting  intruders, 

dimming lights, etc. Besides, if combined with the IRSC controller, presence detectors 

contribute to energy saving by switching the A/C system off when the room is empty. 

 

Figure 12. 

Presence Detector 

Activating  this  feature  brings  the  1-bit  "Presence  detection"  object,  which  should  be 

linked  to  the  presence  detection  object,  so  that  it  is  aware  of  presence/no  presence 

changes. 

Also the 

"Waiting Period"

 parameter becomes visible, and defines the time period (in 

minutes) that IRSC Plus should wait after receiving the value "0" (empty room) through 

the detection object before switching the A/C unit off. 

As  soon  as  the  "Presence  detection"  object  receives  the  value  "1",  IRSC  Plus 

considers the room is again occupied, so if the value "0" arrives again, the time count 

will start again. 

Note:

 

during the “no detection” state, the device will still accept requests from the bus 

and update its objects according to them. Although the machine is off, as soon as it is 

switched  on  again,  IRSC  will  send  the  proper  commands  to  update  its  state  as 

corresponding.  Because  of  this,  in  the  particular  case  of  receiving  a  switch-off  order 

under  “no  detection”  (therefore,  being  the  machine  already  off),  a  later  presence 

detection will not make the A/C unit turn on again as IRSC will then send an order to 

switch it off. In such case, an explicit ON order will be required. 

Содержание IRSC Plus

Страница 1: ...IRSC Plus Air Conditioning Controller ZN1CL IRSC USER MANUAL Application program version 6 12 8 0 User manual edition 8 0 _a www zennio com...

Страница 2: ...4 1 3 The IRSC Plus Application Program 6 2 Configuration 7 3 ETS Parameterisation 8 3 1 Default Configuration 8 3 2 General Parameters 11 3 3 Status 12 3 4 Reset Initial Configuration 13 3 5 Reset Da...

Страница 3: ...Open Window function 20 6 11 _a Changes in the application program Additional split models available for control 6 10 _a Changes in the application program Additional split models available for contr...

Страница 4: ...ctions into the same device Control of the main functionalities of A C units On Off temperature mode fan speed etc Compatibility with most air conditioning manufacturers please refer to the correspond...

Страница 5: ...ing the associated LED 2 light in red If this button is held while plugging the device into the KNX bus IRSC goes into safe mode IR emitter 5 infrared flashing diode to send commands to the air condit...

Страница 6: ...common air conditioning systems via IR commands This application allows sending control orders to the A C system through infrared commands with IRSC acting as a KNX IR interface as explained in Secti...

Страница 7: ...ver the following functionalities of the A C system can be configured ON OFF control of the A C system Status Objects which also work as acknowledgement objects for the orders sent to the system Worki...

Страница 8: ...nt functionalities of IRSC Plus in ETS 3 1 DEFAULT CONFIGURATION This section shows the default configuration the device parameterisation starts from for the first time Figure 4 IRSC Plus Default Topo...

Страница 9: ...iving a 1 through this object will make the slats swing i e perform a progressive sweep while one 0 will make them stop In the case of machines that permit multiple still positions for the slats the a...

Страница 10: ...sed control orders which can be done by sending a 1 to its corresponding IRSC controller through the address of the Disable device object On the other hand when IRSC Plus is parameterised for the firs...

Страница 11: ...to be controlled These are the following Split Model sets a code between 0 and 255 associated to the model of the IR remote of the system to be controlled please refer to the correspondence table at h...

Страница 12: ...meterised temperature limitation effectively applied in such case the system will always keep the setpoint over the lower limit for Cool mode and under the upper limit for Heat mode truncating it when...

Страница 13: ...tain integer value according to the currently active mode according to Table 2 Fan enables the Fan status 1 byte object which shows the current fan speed in percentage of the A C system according to T...

Страница 14: ...wever after a download or a device reset from ETS the previous status will be lost during the download or the device reset in such case IRSC Plus will assume ON OFF Off Temperature 25 C Mode Cool Fan...

Страница 15: ...or a device reset the status of the slats can be set to Last saved status1 Swing or Stopped Note that for both a default and for a custom configuration the Send Reset Configuration to the Split when r...

Страница 16: ...the state sent to or assumed in the A C system after a bus interruption a download or a device reset This is done from the Reset Data Update screen Figure 8 Reset Data Update It is possible to select...

Страница 17: ...cts should have been enabled see section 3 3 in order to have these values effectively sent to the bus Important if this sending is not enabled the KNX bus will definitively not be informed about the...

Страница 18: ...mosphere to be generated Scene Number the numeric value 1 to 64 on whose arrival from the bus through the Scenes 1 byte object decreased by one 0 to 63 the air conditioning system will execute the sce...

Страница 19: ...n and off can be independently enabled and configured After activating the Automatic OFF the Fixed Auto OFF 1 bit object will appear and the following parameters will also be shown in ETS Automatic OF...

Страница 20: ...igured waiting period and then it will send a switch off order to the A C system When the window is closed again Window sensor 0 the A C system will be automatically switched on it will not be necessa...

Страница 21: ...the time period in minutes that IRSC Plus should wait after receiving the value 0 empty room through the detection object before switching the A C unit off As soon as the Presence detection object rec...

Страница 22: ...1IR ZAS and ZN1IRZ38 of any of the various Zennio devices capable of receiving IR signals ZAS InZennio Z38i ACTinBOX Hybrid ACTinBOX MAX6 or ACTinBOX QUATRO One of these devices will be therefore requ...

Страница 23: ...er device ZAS InZennio Z38i ACTinBOX Hybrid ACTinBOX MAX6 or ACTinBOX QUATRO of the signals generated by the emitter and therefore whether IRSC Plus is behaving anomalously or not Important it is high...

Страница 24: ...T W U DPST 1 1 DPST 1 10 0 1 Swing 1 Swing 0 Stop Step 7 1 Bit O C T R DPST 1 1 DPST 1 10 0 1 Swing status Swing state 0 Stopped 1 Swing 8 1 Bit I C T W U DPT_Switch 0 1 Heat Mode 1 Set mode 0 Nothing...

Страница 25: ...Auto OFF 1bit 1 Sw OFF after param value 23 1 Bit I O C R W U DPT_Start 0 1 Fixed Auto ON 1bit 1 Sw ON after param value 24 1 Bit I C W U DPT_Bool 0 1 Presence Detection 0 Empty Room 1 Presence 25 1...

Страница 26: ...d us your inquiries about Zennio devices http suppot zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 Fax 34 925 337 310 www zennio com info...

Отзывы: