WIRING DIAGRAMS 

Figure 1: Wiring example (from top to bottom and left to right): 2 loads, 2 loads connected to different phases, shutter channel, 

fan coil three-speed fan, fan coil three-point valves and fan coil open/close valves. 

* In case of using ZN1IO-DETEC-P sensor, its micro switch number 2 must be in 

Type B position

** Zennio temperature probe or any NTC with known resistance values at three points in the range [-55, 150ºC]. 

INPUTS CONNECTION 

Any combination of the following 

accessories

 is allowed in the inputs: 

Zennio  temperature 
probe.

 

 

 

Up  to  two  motion  sensors 
can  be  plugged  into  the 
same  device  input  (parallel 
wiring)

 

 

 

Screw 

terminal 

for 

connecting  Zennio  motion 
sensors*.

 

 

Temperature Probe**

 

Motion Sensor

 

 

 

Switch/Sensor/ 

Push button

 

 

 

 

INPUTS SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Number of inputs 

Inputs per common 

Operation voltage 

+3.3VDC in the common 

Operation current 

1mA @ 3.3VDC (per input) 

Switching type 

Dry voltage contacts between input and common 

Connection method 

Screw terminal block 

Cable cross-section 

0.5-2.5mm² (IEC) / 26-12AWG (UL) 

Maximum cable length 

30m 

NTC probe length 

1.5m (up to 30m) 

NTC accuracy (@ 25°C) ² 

±0.5°C 

Temperature resolution 

0.1°C 

Maximum response time 

10ms 

² For Zennio temperature probes. 

 

 

 In order to ensure the expected status of the 

relays,  please  check  that  the  device  is 
connected  to  the  main  power  supply  before 
energizing the power circuit. 

For  a  4-pipe  fan coil,  the  cooling  valve  should 
always  be  connected  on  the  left  side  and  the 
heating valve on the right side. Before the start-
up of the device, it must be assured that the valve 
is completely closed. 
 
The  fan  and  the  valves  to  be  connected  must 
have the same nominal supply voltage. 
 
Outputs that are not being used for valve control 
can  be  used  as  individual  outputs  or  shutter 
channels. 
 
 

V1

V2

B2

C1

L/G

N/G0

ABRIR

CERRAR

ABRIR

CERRAR

B2

C1

C2

D1

D2

L/G

N/G0

A1

A2

B1

I

II

III

L

N

A1

A2

L1

N

L2

B1

A2

  

 

 

A2

 

 

OPEN

 

CLOSE

 

OPEN

 

CLOSE

 