Zencontrol zc-switch Скачать руководство пользователя страница 1

Dimensions

Dimensions

40 / 20 / 10.5 mm

Specifications

Supply voltage

9.5 - 22.5 V dc (supplied from DALI)

Control system

DALI-2

Supply current

5 mA

Input

2 floating dry contacts

Note: Any switch used shall be LV rated

Output

FELV 3.3 V logic level output,

max. current 1 mA

Wiring

0.5 - 0.75 mm

2

Strip 6 - 7 mm

Operating temperature

0 to 45°C

Material

PC

Ingress protection

IP20

Product range

Order code

Description

zc-switch

DALI-2 switch module, 2 configurable I/O

Installation

Remove the product from the box and inspect it for any damage. If 

you believe the product to be damaged or otherwise unsound, 

do not

 

install the product. Please pack it back into its box and return it to the 

place of purchase for replacement. 

If the product is satisfactory, proceed with the installation: 

Ensure safety warnings are adhered to

.

Connect the two DALI terminals to the DALI line ensuring wiring

 

regulations are followed. DALI is not polarised. DALI is not SELV 

and as such must be treated as LV. 

Do not connect the switch to 

any mains voltages.

Connect the momentary switch(es) to the floating contact inputs 

(A/B). Only connect one momentary switch per input. 

 

Do not

 connect momentary input to mains voltage.

Install switch behind the wall-plate or mounting enclosure for 

momentary switch. 

Note

 default configuration is A/B input. 

Configuration dependant on DALI-2 application controller.

40

20

10.5

System overview

W

allpl

at

e

zc

-c

ontr

oller

zc

-psu

DA

LI

 luminair

e

Ethernet

D

ALI 2.0

L

N

LN

LN

zc-

re

la

y

Load

L

Lʼin

Lʼout

N

L

N

zc

-swit

ch

zc

-pir

L N 

DA     DA

N

L′

 out

L′

 in

DA     DA

Safety information

 

This product must only be installed by a licensed electrician.

 

Before commencing installation turn off and isolate the 

electrical supply.

 

There are no user serviceable parts, attempting to service any 

part of the product will void the warranty

 

The switch must not be connected to any mains. It is 

powered directly from the DALI line.

 

DALI is not SELV and as such should be treated as LV.

 

As the installer, it is your responsibility to ensure you comply 

to all relevant building and safety codes. Refer to application 

standards for the relevant rules.

 

When the installation is complete, leave this manual with the 

building’s owner for future reference.

 

The installer must protect against accidental contact, all 

terminals are not safe to touch.

 

 There is no isolation between the control terminals and 

supply. Outputs should be treated as LV.

Wiring diagram 

COM

Switch

LED

DA
DA

A

B

COM

Switch

Switch

DA
DA

A

B

A

B

Input configuration (default)

Input / output configuration

Wire preparation

6 - 7 mm

0.5 -  0.75 mm

2

DALI-2 switch module  

zc-switch

Отзывы: