13
Conversion to SELV
The installation must be carried out by a qualified electrician.
A double-pole switch having a minimum contact separation of 3mm must be used
to provide isolation for the unit.
The recommended alternative ‘switch-live’ switch for use is the GS2 switch
(see section 2.6.6). (Not to be used when product is commissioned in intermittent
mode).
The fan must not be mounted above or closer than 1m to the cooker where it
could be affected by excessive heat or moisture.
Wiring Details SELV 24V DC Model
• Unclip cables from the connector on the Power Supply.
• Unscrew the two screws holding the SELV Back Plate to the OF100GIP.
• Once the SELV Back Plate and Power Supply has been removed the cables
that have been unclipped need to be docked into the designated docking point
on the Back Plate (A).
SELV Box Installation
• Install SELV Back Plate and Power Supply in a suitable location outside of the
splash zones, preferably outside the room where the OF100GIP fan is installed.
The location should be as such that air can circulate around the Power Supply
unit and it should never be covered.
• The distance between the fan and the SELV Back Plate and Power Supply
should be kept to a minimum and ideally not be greater than 3.0m.
• Strip cable to correct lengths as shown in Figure 2.a (section 2.6.9) for
both fan and SELV Back Plate.
2.7
2.7.1
2.7.2
2.7.3
2.7.4
2.7.5
Remove Screws
Docking wiring loom
Remove SELV Back Plate
and Power Supply
A
Unclip cables from this
connector