background image

27

periodically using a brush and 
vacuum cleaner, taking care not 
to dislodge the factory applied 
balancing weights on the blower 
wheel blades. Clean the blower 
at every inspection. Any blower 
or motor that is not properly 
maintained will not be covered 
under the manufacturer’s 
warranty. 

Electric heating element Finned 
tubular type heaters generally 
require no normal periodic 
maintenance when unit air filters 
are changed properly. The 
operation and service life may 
be affected by other conditions 
and equipment in the system. 
The two most important operating 
conditions for an electric heater 
are proper airflow and proper 
supply voltage. High supply 
voltage and/or poorly distributed 
or insufficient airflow over the 
heater will result in the element 
overheating. This condition may 
result in the heater cycling on 
the primary automatic high limit 
thermal cutout. If the temperature 
becomes too high, the secondary 
high limit thermal cutout may be 
activated, breaking the circuit and 
leaving the unit non-operational.  
 
The primary automatic thermal 
cutout will reset automatically 
after the heater has cooled 
down, allowing the unit to run 
again without intervening. 
The secondary thermal cutout 
is a safety device only, is 
not intended for continuous 
operation and will need to be 
replaced before the unit will 
operate again. With proper unit 
application and operation, the 
primary high limit thermal cutout 
will not operate. This device only 
operates when there is a problem 

and ANY condition that causes the 
high limit cutout to operate MUST 
be corrected immediately. High 
supply voltage also causes excessive 
amperage draw and may trip the 
circuit breaker or blow the fuses on 
the incoming power supply. 
 
After proper airflow and supply 
power are verified, regular filter 
maintenance is important to provide 
clean air over the heater. A dirty filter 
will inhibit the proper airflow, leading 
to high temperature situations. 
Improper filtration will also lead to 
dirt being deposited on the heating 
element, causing hot spots and 
eventual element burn through. 
These hot spots will generally not 
be enough to cause the high limit 
switches to trip and may not be 
evident until the element actually 
fails. Dirt deposited on the element 
will also cause unwanted odors in the 
air-conditioned space as the foreign 
material is burned off. 

Electrical wiring & controls

T

he electrical operation of each unit 

is determined by the components 
and wiring of the unit. This may vary 
from unit to unit. Refer to the wiring 
diagram located in a zip-lock plastic 
bag on the air block-off plate of each 
unit for the actual type and number 
of controls provided on each unit. 
 
The integrity of all electrical 
connections should be verified at 
least twice during the first year of 
operation. Afterwards, all controls 
should be inspected regularly for 
proper operation. Some components 
may experience erratic operation or 
failure due to age. Thermostats may 
become clogged with dust and lint, 
and should be periodically inspected 
and cleaned to provide reliable 
operation. 
 
When replacing any electrical 
components such as fuses, 
contactors, relays or transformers, 

use only the exact type, size 
and voltage component as 
furnished from the factory. Any 
deviation from this could result 
in personnel injury or damage 
to the unit. This will also void 
the manufacturer’s warranty. All 
repair work should be done in 
such a way as to maintain the 
equipment in compliance with 
governing local and national 
codes, ordinances and safety 
testing agency listings. 

Valves and piping

No formal maintenance is 
required on the valve package 
components other than a visual 
inspection for possible leaks 
during normal periodic unit 
maintenance. Strainers, when 
included, should be checked 
regularly for build-up and rinsed 
as needed. In the event that a 
valve should need replacement, 
the same precautions taken 
during the initial installation 
to protect the valve package 
from excessive heat should be 
implemented during replacement

Throwaway filters

These types of filters should 
be replaced on a regular basis. 
The time interval between 
replacement is dependent upon 
the environment in which the 
unit is operating and should 
be set established based on 
regular inspection of the filter. 
Record the time interval in the 
maintenance log for future 
reference. Refer to the product 
catalog for the recommended 
filter size. If the replacement 
filters are not purchased from 
the factory, the same type and 
size filters should be obtained. 
MERV9 or higher pleated media 
or extended surface filters 
should not be used without 
consent from the factory due 
to the high air pressure drops 

Maintenance

Maintenance

Содержание FVH series

Страница 1: ...i Cooling Fresh Air Clean Air Heating Vertical Hi Stack Fan Coil Installation Operation and Maintenance...

Страница 2: ...k connections 16 Wiring diagram 17 Electrical connections 19 Enclosing unit 20 Start up 22 Water systems 23 EC Motor 25 Control operations 25 Maintenance 26 Replacement parts 28 Troubleshooting 29 Equ...

Страница 3: ...shown in diagrams to the right Outside air available on left or right side of unit opposite riser side Available on both sides with back riser location Optional riser chase available for hideaway unit...

Страница 4: ...78 6 Heating capacity optional 1 row reheat coil MBH 19 9 23 7 31 6 38 6 48 6 52 0 GPM 2 1 2 4 3 2 4 0 4 9 5 3 PD ft of H2 O 7 5 10 3 17 3 7 1 10 9 12 3 Heating capacity optional 2 row reheat coil MB...

Страница 5: ...ulation Condensate insulation 2 1 2 1 2 3 4 1 2 2 1 2 1 1 2 2 1 2 1 1 2 1 2 1 1 2 3 4 3 4 1 2 1 1 4 3 4 1 1 2 1 3 4 1 1 4 1 2 1 1 4 3 4 3 4 3 4 1 3 4 1 3 4 Notes All dimensions are in inches All dimen...

Страница 6: ...by others in field Risers available from 3 4 to 2 1 2 diameter with 1 2 or 3 4 thick insulation Riser length is 104 115 standard Back riser location shown See arrangement drawings for available unit c...

Страница 7: ...del FVS slave Notes All dimensions are in inches All dimensions are 1 4 Wiring from electrical entry point to control enclosure is furnished and installed by others in field Outside air damper opening...

Страница 8: ...ceptable riser combinations Supply Return Insulation Condensate Insulation 2 1 2 1 2 3 4 1 2 2 1 2 1 1 2 2 1 2 1 1 2 1 2 1 1 2 3 4 3 4 1 2 1 1 4 3 4 1 1 2 1 3 4 1 1 4 1 2 1 1 4 3 4 3 4 3 4 1 3 4 1 3 4...

Страница 9: ...notice Dimensional data Grille size A B C D 14 x 16 17 11 16 15 11 16 15 11 16 13 11 16 12 x 14 15 11 16 13 11 16 13 11 16 11 11 16 7 x 16 17 11 16 15 11 16 8 11 16 6 11 16 6 x 14 15 11 16 13 11 16 7...

Страница 10: ...untersunk screw holes Standard finish is powder coated and will be the same color as the return grille Mounting hardware included All listed dimensions are approximate and are subject to change withou...

Страница 11: ...eturn air grille Notes Frame and return grilles are shipped loose for field installation Optional grille does not come with a frame Contact the factory regarding extended front panels for additional c...

Страница 12: ...drilling cutting or working with chemicals Never pressurize equipment beyond specified pressures as shown on unit rating plate Always pressure test with an inert fluid such as water or dry nitrogen to...

Страница 13: ...for personal injury or property damage resulting from improper or unsafe practices during the handling installation service or operation of the equipment The installation of fan coils and all associat...

Страница 14: ...he customer to provide the protection necessary to prevent vandalism and weather deterioration of the equipment Under no condition should the units be left unprotected from the elements The equipment...

Страница 15: ...As the unit is righted align the risers with the unit below In the case of shipped loose risers install from the lowest floor to the highest floor After the risers are field tested for leaks the Fan C...

Страница 16: ...inside the unit so condensate if formed will run back into the condensate pan and not out toward the riser Any water damage caused by not following this procedure is not covered under the warranty Mak...

Страница 17: ...lowing this procedure is not covered under the warranty The riser connection joints should be hydrostatically tested for leaks before furring in the unit Pressure of water column alone is approximatel...

Страница 18: ...tment Such recommendations will be made by the factory upon request All ductwork and or supply and return grilles should be installed in accordance with the project plans and specifications If not inc...

Страница 19: ...ED FACTORY WIRED 18AWG FACTORY WIRED 12AWG Wiring diagram 120V Standard blower motor wiring chart Size High Medium Low Capacitor Capacitor size 03 Red Blue Black Gray Yel 5 F 04 Blue Black Brown Gray...

Страница 20: ...ture sensor is used wire to thermostat tb1 terminals 1 and 2 High static blower motor wiring chart Size High Medium Low Capacitor Capacitor size 03 Blue Black Brown Gray Yel 1 5 F 04 Red Blue Black Gr...

Страница 21: ...trical Code and any applicable local codes Branch circuit fusing and electrical disconnect means if required must be furnished and installed by others All unit mounted control components and electrica...

Страница 22: ...When cutting out supply and return holes for grilles be sure to clean all drywall dust from coils drain pans and blower discharge plenum After drywall is in place and rooms are prepared for final wal...

Страница 23: ...l and stud mounting lines Install drywall to sides of unit with optional cut outs for supply outside air and thermostat Install drywall to face of unit with optional cut outs for supply return and the...

Страница 24: ...acturer s warranty Start up Before beginning any start up the start up personnel should take the time to familiarize themselves with the unit options accessories and control sequence to fully understa...

Страница 25: ...not release air trapped in other parts of the system Inspect the entire system for potential air traps and independently vent those areas as required In addition some systems may require repeated vent...

Страница 26: ...Before and during water system balancing conditions may exist due to incorrect system pressures which may result in noticeable water noise or undesired valve operation After the entire system is balan...

Страница 27: ...tentiometers marked as FL01 FL02 FL03 to adjust the airflow associated with each input Each output can be adjusted from 0 to 100 of the motor s factory programmed operating range using an instrument s...

Страница 28: ...l result in rapid corrosion of the metals Strong alkali base cleaners pH of 11 or more containing sodium potassium or ammonium hydroxide are not recommended as they will aggressively corrode aluminum...

Страница 29: ...lement will also cause unwanted odors in the air conditioned space as the foreign material is burned off Electrical wiring controls The electrical operation of each unit is determined by the component...

Страница 30: ...to allow proper flow of condensate Failure to strictly follow this instruction will void the manufacturer s warranty and the manufacturer will not be responsible for any consequential damages due to w...

Страница 31: ...activated drain pan clogged Remove debris from drain pan unclog pan unclog drain and emtpy Unit blows fuse when power is applied to unit Defective or improperly wired component Using a battery powered...

Страница 32: ...operates but air delivery is low Incorrect fan speed has been selected Re select proper fan speed as required Dirty air filter Replace air filter Dirty coil Clean coil Obstruction in ductwork Check f...

Страница 33: ...limit trips again check for the following conditions improper voltage to heating element obstructed fan or unit outlet reducing air flow over heating element dirty or defective heating element causing...

Страница 34: ...grilles as required n n Flexible duct connections at unit n n Proper supply and return grille type and size n n Control outside air for freeze protection n n Insulate all ductwork as required Electric...

Страница 35: ...of written consent from Zehnder Rittling the purchaser shall return the defective good s to the factory for inspection with freight prepaid If inspection shows the goods to be defective Zehnder Rittl...

Страница 36: ...tling 100 Rittling Boulevard Buffalo NY USA 14220 T 844 934 6337 844 ZEHNDER F 716 827 6523 sales zehnder rittling com www zehnder rittling com Zehnder Rittling May 2015 English subject to change with...

Отзывы: