The commissioning wizard will ask you to set the following information in the second part:
Screen
Function
MAXIMUM FLOW
The unit instructed you to prepare the system for a maximum flow test.
When opening all valves also open all grilles and close all windows and doors.
ARE ALL VALVES
COMPLETELY OPEN?
The unit will ask you if the system is ready for the maximum airflow test before starting the
test.
MAXIMUM FLOW
After the maximum flow test is completed the unit will tell you the expected maximum flow
of the system.
INSTRUCTION
The unit will ask you not to change the preparations you made for the maximum flow test till
instructed.
MEDIUM AIR FLOW
Select the desired airflow for PRESET 2.
MAXIMUM AIR FLOW
Select the desired airflow for PRESET 3.
LOW AIR FLOW
Select the desired airflow for PRESET 1.
AWAY AIR FLOW
Select the desired airflow for PRESET A.
The unit will use this setting in the medium airflow test.
COMMISSIONING AIR FLOW
Select the desired airflow in which you would like to commission the valves and/or grilles.
FINE TUNE ALL EXTRACT
AND SUPPLY VALVES
Use a flow meter to set the valves and/or grilles into the correct position. Start with the
valve or grille farthest from the unit and work back along the air duct to the unit.
ARE ALL VALVES FINE
TUNED
The unit will ask you if all valves and/or grilles are commissioned before checking the
maximum air flow.
CHECK AIRFLOW
The unit will warn you if the selected maximum air flow is unable to be achieved.
It is recommended you adjust the system to reduce the pressure drop and enable the
required airflow rate to be achieved. You can also ignore this information.
END OF THE INSTALLATION
WIZARD
The unit will tell you that the commissioning wizard is completed and will store all settings
after confirmation.
Please help the user by also setting the advanced user menus for them, like for instance the SENSOR
VENTILATION settings.
In the user manual you can find how to set the advanced menus.