5.4.3.1.
Configuring the Meter parameters
After connecting the cables correctly, it is necessary to set the correct parameters from the Meter
display.
Figure 74 - Meter Legend
Exchange Meter configuration
To configure the device in read mode on
exchange
, enter the settings menu as shown below:
1.
Press
SET
and the word
CODE
will appear
2.
Press
SET
again and the number “600” will appear:
3.
Enter the number “701”:
a.
From the first screen where the number “600” appears, press the “→” key once to write
the number “601”.
b.
Press “
SET
” twice to move the cursor left, highlighting “601”;
c.
Press the “→” key once more to write the number “701”
Note
: In case of error, press “ESC” and then “SET” again to reset the required code.
1.
Press to:
“Confirm”
Move cursor
(to enter digit)
2.
Press to “go back”
3.
Press to “add”