Technical specifications
TECHNICAL DATA
1PH HYD 3000
ZP1
1PH HYD 3600
ZP1
1PH HYD 4000
ZP1
1PH HYD 4600
ZP1
1PH HYD 5000
ZP1
1PH HYD 6000
ZP1
DC photovoltaic input
Typical DC power *
4500W
5400W
6000W
6900W
7500W
9000W
Independent MPPTs/Strings each MPPT
2/1
Maximum DC voltage
550V
Start-up voltage
100V
Nominal DC voltage
360V
MPPT range in DC
85V-520V
Maximum DC input current each MPPT
16A/16A
Maximum absolute DC input current each MPPT
22.5A/22.5A
Battery input data
Type of batteries
HV ZBT 5K + BDU Unit
Nominal voltage
400V
Voltage range
300V-435V
Maximum charge/discharge power
3000W
3680W
4000W
4600W
5000W
6000W
Allowed temperature range**
-10°C/+50°C
Maximum charge current
20A (setabke)
Maximum discharge current
20A (setable)
Charge curve
Managed by integrated BMS
Depth of Discharge (DoD)
0%-90% (setable)
AC output
Nominal AC Power
3000W
3680W
4000W
4600W
5000W
6000W
Maximum AC Power
3300VA
3680VA
4400VA
4600VA
5500VA
6600VA
Maximum AC current each phase
13A
16A
17.4A
20A
21.7 A
26A
Type of connection/Nominal AC grid voltage
Single phase L/N/PE 220,230,240V
AC voltage range
180V-276V
(according to local standards)
Nominal AC frequency
50Hz/60Hz
AC frequency reange
44Hz-55Hz / 54Hz-66Hz
(according to local standards)
Total Harmonic Distortion (THD)
< 3%
Power Factor
1 default (/- 0.8)
Active power grid injection
Setable by display
EPS (Emergency Power Supply) output
Maximum Power in EPS***
3000VA (4500VA
for 10s)
3680VA (5520VA
for 10s)
4000VA (6000VA
for 10s)
4600VA (6900VA
for 10s)
5000VA (7500VA
for 10s)
6000VA (9000VA
for 10s)
Voltage and frequency in EPS
Single phase 230V 50Hz/60Hz
Maximum current in EPS
13A
16A
17.4A
20A
21.7 A
26A
Total Harmonic Distortion (THD)
< 3%
Switch time
< 10ms
Efficiency
Maximum Efficiency
97.7%
97.8%
Euro efficiency
97.0%
97.1%
Efficiency MPPT
>99.9%
Standby consumption
< 10W
Protections
Internal interface protection
Yes
Safety protections
Anti islanding, RCMU, Ground Fault Monitoring
DC reverse polarity protection
Yes
DC switch
Integrated
Overheating protection
Yes
Overvoltage catergory/Protection class
Overvoltage Category III (AC) / II (DC) / Protective class I
Integrated dischargers
AC/DC MOV: Type 3 standard
Battery Soft start
Yes
Standard
EMC
EN 61000-3-2/3/11/12, EN 61000-6-2/3
Safety standards
IEC 62116, IEC 61727, IEC 61683, IEC 60068-1/2/14/30, IEC 62109-1/2
Grid standards
Grid standards and certificates available on www.zcsazzurro.com
Communication
Communication Interfaces
Wi-Fi/4G/Ethernet (optional), RS485 (
proprietary protocol
), USB
Additional connection
AC Current sensor connection input or dedicated meter
Environmental data
Temperature working range
-10°C...+50°C (power derating over 45
℃
)
Topology
Trasformerless
Environmental protection degree
IP65
Humidity range
5%.....95% no condensing
Maximum operative altitude
4000m
Acustic noise
< 35dB @ 1mt
Weight
22.5Kg
Cooling system
Natural cooled
Dimensions (H*W*L)
410mm*708mm*170mm
Display
LED display and APP
Warranty
10 years