User’s Manual 1PH HYD3000-HYD6000-ZP1
Rev. 1.0 01/09/2023
Identification: MD-AL-GI-00
Rev. 1.1 of 27/01/2023 - Application: GID
115/193
10.6.8.
Parallel Setting
For the parallel system, please refer to <4.6 Parallel System > .
6.Parallel
Setting
1.Parallel function
control
2.Parallel Primary-
Replica
3.Set Parallel Address
4.Save
1.
Parallel function control: Enable or disable the parallel function. This function must be enabled on both the
master and slave machines.
2.
Set master and slave: Set the master and slave. Select one inverter as the master and the others as slave
machines.
3.
Set parallel address: Set the parallel address for each inverter. In a parallel system, each inverter should have
a parallel address that does not duplicate that of other machines. (Note: Parallel addresses are different from
communications addresses used for monitoring.)
4.
Save: Be sure to save after the Settings.
10.6.9.
Bluetooth Reset
7.Bluetooth
Reset
Please
Confirm
!
Succeed
10.6.10.
CT Calibration
Used to calibrate the orientation and phase of the CT. The battery should be charged or discharged when using
this feature.
For the inverter to perform this operation, it is necessary that:
•
The system is connected to the grid
•
The load output is not powered
•
The batteries are present and switched on and at a maximum SOC of 40% to 80% (with depth of
discharge ≤ 20%)
•
The loads in the system are switched off
•
Photovoltaic production is switched off
•
Any other external production sources are switched off
8.CT Calibration Start CT
Calibration
Succeed/F
ailed
Set CT Power
Offset
***W
10.6.11.
Set ElectricityMeter
10.Set
ElectricityMeter
Disable
Enable