Depth of Discharge
For example: if Discharge Depth = 50% & EPS Discharge Depth = 80%.
While grid is connected: Inverter won’t discharge the battery when its SOC is less than 50%.
In case of blackout: Inverter will work in EPS mode (if EPS mode is enabled) & keep discharging the battery
till battery SOC is less than 20%.
3.Depth of
Discharge
Discharge Depth
50%
EPS Discharge Depth
80%
EPS Safety Buffer
20%
10.6.3.
Battery Actiovation
2.Battery Activation
1.Auto Active Control
2.Force Active
10.6.4.
Anti Reflux
“Up” ↑
“Down” ↓
The user can enable the “Anti Reflux Control” to limit the maximum energy exported to the grid. Select “2. Reflux
Power” to enter the maximum amount of energy exported to the grid.
5.Anti Reflux control
***KW
2.Reflux Power
Disable
Enable
1.Anti Reflux control