7.
Troubleshooting and maintenance
7.1.
Troubleshooting
This section contains information and procedures on how to troubleshoot any faults and errors that may
occur during operation of the 1PH 2700TL-3300TL-V3 inverter.
If you have any problems with the inverter, please follow these steps.
Check the warning messages and error codes on the information panel of the inverter. Record them
before carrying out any further operation.
If the inverter does not display any errors, perform the following checks:
-
Is the inverter located in a clean, dry and properly ventilated place?
-
Is the DC switch closed?
-
Are the cables correctly sized and as short as possible?
-
Are the input/output connections and the cables in good condition?
-
Are the configuration settings correct for the type of installation?
-
Are the display and flat cable correctly connected and not damaged?
Follow the steps below to display the recorded alarms:
Long press the key to enter the main menu from the standard interface. Select “Event List” in the menu
screen, then long press the key to access the list of alarms and errors.
Information on event list
Error
code
Error name
Error description
Possible solution
ID01
GridOVP
The grid voltage is too
high.
If the alarms occurs occasionally, the
probable cause is that the electric
grid is in an abnormal state.
The inverter will automatically
return to its normal operating state
when the electrical grid is restored to
ID02
GridUVP
The grid voltage is too
low.