background image

 
 
 

 
 

  
 

 

Page. 8 

LMV2635.EN.202001_V2 

 

 

5. START SEQUENCE 

When the gas pressure is nominal, the correct power is supplied to the control 
panel, the safety valves are 

closed, the on/off thermostat emits an “on” signal and 

all other boiler values are within the limits, the burner will start when the burner 
on/off switch is set to 1. 
The start-up sequence is as follows: 
 

 

A.

  After switching the system on, the air fan starts at low speed, sometimes after a 

short delay. 

 

B. 

Once the air fan is at nominal speed, the servomotor of the air quantity control 
valve (pos. HR2) opens fully. When the servomotor that controls the air quantity 
control valve doesn’t make the complete pre-set stroke, the air quantity control 
valve will not be sufficiently opened. The burner will be shut off and the system 
goes into lockout. An error message is displayed. The air fan will be set to 
maximum speed (50 Hz) approximately linear to the air valves to ventilate the 
system. 

 

C.

  If the air quantity control valve is opened the pre-purge cycle starts. During the 

30 seconds pre-purge cycle the boiler furnace is ventilated, to clear any 
remaining flue gas. During the pre-purge cycle the position of the air quantity 
control valve and of the air pressure are checked continuously. 

 

D.

  At the end of the pre-purge cycle the air fan is set to low speed (+/- 25 Hz) and 

the air quantity control valve is positioned to the start/low flame position. 

 

The gas quantity control valve (pos. HR1) controlled by a servomotor is also 
positioned to the start/low flame position. The minimum air pressure is checked 
during operation by a second air pressure switch (pos. LD2 low). 

 

F. 

All the air and gas controls are in now in the start position. The next step is to 
light the pilot flame. A few seconds after reaching the start position the ignition 
transformer is switched on. It make an electrical spark between the ignition 
electrodes. 
 

G. 

After three (3) seconds the pilot gas valve (pos. MK) opens and the spark lights 
the gas. After another five (5) seconds the flame monitoring device checks 
whether the UV scanner detects a pilot flame. The 5 seconds period during 
which the pilot flame is lighted is called the first safety time. At the end of the 
first safety time the pilot flame should be burning stable and the electrical spark 
is switched off. The flame monitoring unit checks the flame continuously during 
operation. 
 If the flame is not formed in the first safety time the flame monitoring unit goes 
into lockout and an error message is displayed on the electronic module. 
 

G.

  If the flame monitoring unit detects the pilot flame, the system continues the 

ignition procedure after a short time period. The main safety valves (pos. VA1 
and VA2) open to ignite the main flame. The pneumatic gas pressure regulator, 

Содержание TR-LMV26

Страница 1: ...YOU CAN COUNT ON OUR EXPERTISE OPERATING AND INSTRUCTION MANUAL ZANTINGH FORCEDGASBURNER TR RKB LMV26 3 5 SAMBA...

Страница 2: ...tem Contents Page 1 INTRODUCTION 3 2 REGULATION 3 3 IMPORTANT NOTES 3 3 1 Maintenance 4 3 2 Instruction manual instructions 4 4 SYSTEM COMPONENTS 5 4 1 Burner component 5 4 2 Air fan component 5 4 3 G...

Страница 3: ...ertified heating or electrical installer should instal the product The instructions meet the applicable local standards and regulations Please contact your Zantingh representative or local service dep...

Страница 4: ...end user s responsibility to ensure safety through annual maintenance work on the system according to applicable regulations To ensure the good operation of the heating system the boiler room has to...

Страница 5: ...the required combustion air This air fan has a directly coupled and balanced fan wheel The fan wheel is driven by an electromotor The air fan of a TR burner is directly connected to the air valve sec...

Страница 6: ...ety device pos HD The HD pressure switch monitors the maximum burner boiler capacity and is mounted on the burner head to control the burner load by means of air pressure The settings of the pressure...

Страница 7: ...e control panel includes a few switches and press button valves Fire on off switch Selector switch for load control with the following two options 1 Automatic modulated by load controller 2 External t...

Страница 8: ...e the air fan is set to low speed 25 Hz and the air quantity control valve is positioned to the start low flame position The gas quantity control valve pos HR1 controlled by a servomotor is also posit...

Страница 9: ...on the electronic module The maximum gas pressure switch pos HD1 ensures an easy steady start of the main flame It is only active when starting the flame The minimum gas pressure switch pos LD1 monito...

Страница 10: ...D display with a simple menu structure which displays the status in plain text In order to diagnose possible malfunctions the operation mode failure type and moment are displayed In case of failure be...

Страница 11: ...and A with or simultaneously reset Info and Enter button For navigating in info and service mode Incrementing the selection flashing symbol press button for 1 s Going one menu level down press button...

Страница 12: ...tronics Samba failures display further called Samba is a digital display viewing the status of the precondition circuit safety chain boiler preconditions Main screen Below an image of the main screen...

Страница 13: ...he right bottom corner of the main screen and the following screen is displayed Arrow buttons and Use the arrow keys to view other notifications Back Press the arrow pointing to the left to return to...

Страница 14: ...ates the burner start stop and controls its load based on the requested boiler temperature setpoint The corresponding display integrated in the burner s switch panel casing shows the following values...

Страница 15: ...ly pressure before the gas train by pressing the press button valve pos K2 under the manometer to read the current pressure on the manometer pos M Or check the manometer on the gas supply gas train Th...

Страница 16: ...previous item Check The air fan inlet Maximum temperature and or pressure The boiler is protected against high temperatures and or pressure A maximum thermostat or maximum pressostat device forms the...

Страница 17: ...Frequency control code F When an internal or external frequency control error is triggered the frequency control is switched off and the F symbol error code is displayed followed by a number includin...

Страница 18: ...ng unit or flame signal is too low No main flame Defect safety valve s pos VA1 and VA2 The air gas ratio is not appropriate because of which the air gas mixture does not ignite or even goes out during...

Страница 19: ...tton on the switch panel door The burner will attempt to restart Note The maximum thermostat and the low water protection device may be mechanically locked The reset button on the safety device itself...

Страница 20: ...nlet valve of the condenser on bypass 5 Check that every valve to the oil pump is open and whether the oil pump is filled with oil The complete system has to be filled with oil without any air If this...

Страница 21: ...as inlet valve of the condenser to standard operation 6 Open shut off valve A1 7 Set the main switch on the burner control panel to ON WARNING Before starting the system check the furnace for oil If t...

Страница 22: ...periodically not performed even though the equipment requires it Corrosion has been caused by polluted flue gas to be determined by Zantingh B V If after research is carried out one or more of the ab...

Страница 23: ...way or by any means be it electronically mechanically photocopy or otherwise without prior written consent from Zantingh B V Reprinting the document or any excerpt thereof is forbidden Changes errors...

Страница 24: ...Phone 31 0 297 219 100 Fax 31 0 297 219 199 E mail info zantingh com France Zantingh France SARL 95 rue F de Lesseps F 44150 Ancenis France Phone 33 0 240 83 94 30 Fax 33 0 240 83 96 72 E mail info z...

Отзывы: