7. BURNER FAILURE REPORT 

Gas valves/leak test

 

Before and during every burner start the safety valves (pos. VA1 en VA2) and pilot 
valve (pos. MK1) are checked for leaks. 
Possible causes: 

 

Failure of the “leak test” can indicate that one of the safety valves or the 
pilot valve was not closed during standstill/start period. 

Check:  

 

If bleed valve K1 is closed/gas-tight. 

 

External gas leakage visible (smell/”leak finder”/soap and water solutiony). 

 

Write down the diagnostic code from the burner display. 

 

Gas pressure too low

 

The minimum gas pressure switch (pos. LD1) mounted before the safety valves 
ensures the supplied minimum gas pressure is continuously checked. If the gas 
supply pressure drops lower than 20% of the standard pressure (or another setpoint 
which is considered to be a safe setting by the authorized burner engineer), the 
safety device triggers a system lockout. 
Check: 

 

If manual gas valve (A1) is fully opened. 

 

The gas supply pressure before the gas train, by pressing the press-
button valve (pos. K2) under the manometer to read the current pressure 
on the manometer (pos. M). Or check the manometer on the gas supply 
gas train. This pressure has to be approximately the same as indicated in 
the contract. 

 

If the gas supply pressure is ok, check the gas filter (pos. F1) for dirt 
(close gas valve A1 manually first). 
 

Maximum gas pressure

 

The maximum gas pressure switch (pos. HD), mounted on the burner gas inlet, 
protects the boiler against overloading. The gas pressure on the burner head is 
measures for this purpose. If the pressure is higher than the setpoint value the 
system is locked out. 
Possible causes: 

 

Abnormal outlet pressure of pressure regulator. 

 

Dirty condenser. 

 

Abnormal gas supply pressure. 

Check: 

 

The position of the burner control box (if applicable) were the failure 
occurs. 

 

The condensate drain of the condenser. 

 
Motor overload

 

The control panel includes overload relays to protect the electromotors. In case of 
failure the overload relays have to be reset manually. The overload relay types 
included on our panels, are combined thermal and maximum current protection 
relays. 

Содержание TR-LMV26

Страница 1: ...YOU CAN COUNT ON OUR EXPERTISE OPERATING AND INSTRUCTION MANUAL ZANTINGH FORCEDGASBURNER TR RKB LMV26 3 5 SAMBA...

Страница 2: ...tem Contents Page 1 INTRODUCTION 3 2 REGULATION 3 3 IMPORTANT NOTES 3 3 1 Maintenance 4 3 2 Instruction manual instructions 4 4 SYSTEM COMPONENTS 5 4 1 Burner component 5 4 2 Air fan component 5 4 3 G...

Страница 3: ...ertified heating or electrical installer should instal the product The instructions meet the applicable local standards and regulations Please contact your Zantingh representative or local service dep...

Страница 4: ...end user s responsibility to ensure safety through annual maintenance work on the system according to applicable regulations To ensure the good operation of the heating system the boiler room has to...

Страница 5: ...the required combustion air This air fan has a directly coupled and balanced fan wheel The fan wheel is driven by an electromotor The air fan of a TR burner is directly connected to the air valve sec...

Страница 6: ...ety device pos HD The HD pressure switch monitors the maximum burner boiler capacity and is mounted on the burner head to control the burner load by means of air pressure The settings of the pressure...

Страница 7: ...e control panel includes a few switches and press button valves Fire on off switch Selector switch for load control with the following two options 1 Automatic modulated by load controller 2 External t...

Страница 8: ...e the air fan is set to low speed 25 Hz and the air quantity control valve is positioned to the start low flame position The gas quantity control valve pos HR1 controlled by a servomotor is also posit...

Страница 9: ...on the electronic module The maximum gas pressure switch pos HD1 ensures an easy steady start of the main flame It is only active when starting the flame The minimum gas pressure switch pos LD1 monito...

Страница 10: ...D display with a simple menu structure which displays the status in plain text In order to diagnose possible malfunctions the operation mode failure type and moment are displayed In case of failure be...

Страница 11: ...and A with or simultaneously reset Info and Enter button For navigating in info and service mode Incrementing the selection flashing symbol press button for 1 s Going one menu level down press button...

Страница 12: ...tronics Samba failures display further called Samba is a digital display viewing the status of the precondition circuit safety chain boiler preconditions Main screen Below an image of the main screen...

Страница 13: ...he right bottom corner of the main screen and the following screen is displayed Arrow buttons and Use the arrow keys to view other notifications Back Press the arrow pointing to the left to return to...

Страница 14: ...ates the burner start stop and controls its load based on the requested boiler temperature setpoint The corresponding display integrated in the burner s switch panel casing shows the following values...

Страница 15: ...ly pressure before the gas train by pressing the press button valve pos K2 under the manometer to read the current pressure on the manometer pos M Or check the manometer on the gas supply gas train Th...

Страница 16: ...previous item Check The air fan inlet Maximum temperature and or pressure The boiler is protected against high temperatures and or pressure A maximum thermostat or maximum pressostat device forms the...

Страница 17: ...Frequency control code F When an internal or external frequency control error is triggered the frequency control is switched off and the F symbol error code is displayed followed by a number includin...

Страница 18: ...ng unit or flame signal is too low No main flame Defect safety valve s pos VA1 and VA2 The air gas ratio is not appropriate because of which the air gas mixture does not ignite or even goes out during...

Страница 19: ...tton on the switch panel door The burner will attempt to restart Note The maximum thermostat and the low water protection device may be mechanically locked The reset button on the safety device itself...

Страница 20: ...nlet valve of the condenser on bypass 5 Check that every valve to the oil pump is open and whether the oil pump is filled with oil The complete system has to be filled with oil without any air If this...

Страница 21: ...as inlet valve of the condenser to standard operation 6 Open shut off valve A1 7 Set the main switch on the burner control panel to ON WARNING Before starting the system check the furnace for oil If t...

Страница 22: ...periodically not performed even though the equipment requires it Corrosion has been caused by polluted flue gas to be determined by Zantingh B V If after research is carried out one or more of the ab...

Страница 23: ...way or by any means be it electronically mechanically photocopy or otherwise without prior written consent from Zantingh B V Reprinting the document or any excerpt thereof is forbidden Changes errors...

Страница 24: ...Phone 31 0 297 219 100 Fax 31 0 297 219 199 E mail info zantingh com France Zantingh France SARL 95 rue F de Lesseps F 44150 Ancenis France Phone 33 0 240 83 94 30 Fax 33 0 240 83 96 72 E mail info z...

Отзывы: