A DRAFT OR A PICTURE OF THE HEATING TABLE, SUPPLY TABLE AND ACCESSORIES

DESCRIPTION

GPRU type heating cables are used to protect against freezing. They are laid on the outer surface of 

pipes and valves, the same, the emitted heat allows to protect the inner liquid against freezing. The 

cable is equipped with a temperature regulator which automatically switches on the heating circuit at 

+3°C (*+5°C) and switches off at a temperature of +11°C (*+13°C). The device measures the tem-

perature on the pipe’s surface. In order to give a proper temperature measurement and an appropriate 

response of the heating cable, it is very important to mount properly the temperature regulator on a 

pipe. The measuring surface of a temperature regulator should be maximally equal with the protected 

surface of a pipe. Too little contact of both surfaces can cause a heat damage to the heating cable. The 

way of applying a temperature regulator to the surface of a pipe is shown in the drawing.

Fig. A way of placing a temperature regulator  to the pipe’s surface

The heating cable should be mounted on the pipe by means of cable ties or mounting tapes. In addi-

tion, it is recommended to apply insulations, e.g. heat insulations. Insulation should be made of fl ame 

retardant or noncombustible material.
The GPRU heating cables are designed for outdoor and indoor use. They are made for 230 V nominal 

voltage 230 V and 18 W/m (*15 W/m).
The temperature regulator is placed on the connection of heating and power cables, acting as a me-

chanical connection of the heating and power part of a device.
The supply cable is ended with a plug that is inserted into a 230 V AC socket.

Heating cable GPRU - the set included:

● one-sided 18 W/m (*15 W/m) power supply heating cable connected by means of a temperature 

regulator with w supply cable ended with a plug, 

● installation instruction with the Warranty Card.

Fig. Heating cable with supply cable and a temperature regulator

REMARKS

• During installation it is required to follow in-

structions included in the Heating Cable Man-

ual Instruction

• It is forbidden to mount the cable on pins, 

bolts, screws or other fi xing elements that can 

damage the outer coating of cables.

• The installation of a temperature regulator, 

which is a part of a complete hating cable, 

should be carried out with a particular attention 

so that the measuring surface of a tempera-

ture regulator is closely attached to the pipe.

• The  cable installation base must be smooth 

with no sharp edges or sharp fi xing elements

• Heating unit cannot be mounted on non-uni-

form bases.

• The heating cable should not be installed in 

places with permanent building.

• The heating cable, the supply cable and the 

plug resistance must be measured at least 

twice: after opening the packaging and before 

starting the installation works and after arrang-

ing the heating cable in its fi nal place.

• It is not advisable to install the heating mats if 

the ambient temperature is below + 5°C. 

• Don’t cut the heating cable or its connection 

with power supply cable and the plug.

• The heating cable should not undergo exces-

sive strain and should be protected against 

sharp device damage.

• It is required to make a draft or add pictures of 

the arrangement of the heating cable, power 

supply cable and the connection place of the 

heating cable with power cable (“cold wire”). 

The draft or pictures are an integral part of the 

as-built documentation.

• Heating unit must be supplied by means of a 

device from TN-S electric circuit with RCD (re-

sidual current device) of nominal power supply 

lower than 30 mA. The installation should have 

surge protection.

• The heating cables must not come into con-

tact, cross with each other or other cables 

- this could damage the insulation. The mini-

mum distance between the heating cables 

must not be less than 5 times its diameter. 

• The heating cable must be evenly wrapped on 

the protected surface. 

• The non-detachable supply cable cannot be 

replaced. If the cord is damaged, the equip-

ment is useless.

• The device is not intended to be used by peo-

ple (children) with limited physical, feeling or 

psychic ability or people without experience 

or without the device knowledge unless it is 

under supervision of a person responsible for 

safety or according to installation manual.

• Pay attention to children - they must not play 

with the device.

• Do not instal on pipes with the temperature 

higher than niż 80°C.

• The radius of heating cable bending shall not 

be less than 8 times of its diameter. 

• The heating cable cannot be immersed in any 

liquid.

• The GPRU heating cable is not designed to 

be used on roofs, in gutters, in drain pipes, on 

pavements, stairs and driveways.

TECHNICAL DATA

Heating cable TYPE

GPRU  2 ÷ 20,5 m long

Power supply voltage:

230 V AC / 50 Hz

Unit power: 

18 W/m (* 15 W/m)

Operating temperature:  Automatic thermostat with an operating range of +3÷+11 

o

C (*+5÷+13°C)

(tol/-3 

o

C)

Supply type:

one-sided

Heating cable:

two-wire, shielded

The heating cable is ended with power supply cable at one side with a plug.

MATEC – ELECTRIC ANTIFREEZING SYSTEMS

 

MANUAL INSTRUCTION

ANTIFREEZING HEATING CABLE TYPE 

GPRU

 FOR PIPE PROTECTION

For GPRU-2/15 the thermostat is on the end of the heating cable

* - for heating cable GPRU-2/15 (15W/m)

Heating cable

Supply

cable

with plug

 Temperature 

regulator

(*)

Heating cable

with thermostat
Pipe

Mounting

tape

Mounting

tape

Fully contact thermostat