background image

2-CHANNEL, ASTRONOMICAL DIGITAL 

TIME PROGRAMMER ZCM-32, ZCM-32P/U

 

MANUAL INSTRUCTION

ZAMEL 

Sp. z o.o.

ul. Zielona 27, 43-200 Pszczyna, Poland

Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04

www.zamel.com

, e-mail: [email protected]

plik: inst_ext_en_zcm-32_32PU | modyfikacja: 07.04.2016

FEATURES

TECHNICAL DATA 

DESCRIPTION

● control depending on current time in the 

astronomical cycle,

● night break programme possibility and a 

change of the calculated sunrise / sunset 

time independently for channel 1 and 2, 

● double modular casing with a protective 

cover,

● IN control input,

● LCD with backlight,

● mounting on a TH35 rail.

ZCM-32 digital time programmers are 

used to realize time functions in automa-

tion and control systems. Switching on / 

switching off the device is related to sun-

set and sunrise (official dawn and dusk). 

The  following  information  on  geograph-

ic  coordinates  of  the  clock’s  installation 

place, current date, and time difference 

with regard to the universal time (GMT) 

is  used  to  calculate  the  time  of  sunrise 

and  sunset.  The  system  calculates  the 

so-called official time of sunrise and sun-

set and this is the phase when the upper 

edge  of  the  Sun  touches  the  horizon. 

The  system  is  equipped  with  two  inde-

pendent channels (outputs). The system 

has the function of a programmable night 

break and a possibility to change the cal-

culated sunrise/sunset time in the range 

of  ±120  min  for  each  channel.  The  de-

vice casing construction allows the sys-

tem  to  be  installed  on  a  TH35  rail  and 

additionally  the  casing  can  be  sealed. 

The system structure guarantees battery 

backup of the settings in case of power 

supply failure.

CAUTION:

To protect the programmer’s bat-

tery during storage time, the ZCM-32 

series has a ‘storage mode’ default 

setting with a minimum current con-

The  device  is  designed  for  single-phase 
installation and must be installed in accor-
dance  with  standards  valid  in  a  particular 
country.  The  device  should  be  connected 
according to the details included in this ma-

nual instruction. Installation, connection and control should 
be carried out by a qualified electrician staff, who act in ac-
cordance with the service manual and the device functions. 
In case of casing dismantling, the guarantee is lost and an 
electric shock may occur. Before installation make sure the 
connection cables are not under voltage. Improper transport, 
storage, and use of the device influence its wrong functio-
ning. It is not advisable to install the device in the following 
cases:  if any device part is missing or the device is damaged 
or deformed. In case of improper functioning of the device 

contact the producer.

CAUTION

* not applicable to ZCM-32

** applicable to ZCM-32P/U

 

Input (supply) terminals:  A1, A2

 

Nominal supply voltage: ZCM-32: 230 V AC~(-15 ÷ +10 %)

 

 ZCM-32xP/U: 24 ÷ 250V AC, 30 ÷ 300 V DC

 

Nominal frequency: 50 / 60 Hz

 

Nominal power consumption:  

 

 0,8 W / 1,4 VA – stand-by 

 

 1,8 W / 3,5 VA - channel 1 

 

 and 2 in switched on mode

 

Number of channels:  2

 

Programme:  astronomical (official dawn and dusk)

 

Operation modes:  automatic, manual

 

Summer/winter time change:  automatic, manual 

 

LCD backlight colour:  amber

 

External input:  yes – independent for channel 1 and 2

 

Cooperation with external memory: 

 

 ZCM-32: no

 

 ZCM-32P/U: yes

 

Time measuring accuracy:  max. ± 1 s / 24 h for 25℃

 

Clock battery backup:  3 years

 

Programme battery backup:  10 years

 

Input (release) terminals:  IN1, IN1 – for channel 1

 

 IN2, IN2 – for channel 2

 

Output (load) terminals:  11, 12, 14 – channel 1; 21, 

 

 22, 24 – channel 2

 

Relay contact parameters:  2 NO / NC 16 A / 250 V AC1 4000 VA 

 

Number of connection terminals:  12

 

Cross-section of connection cables:  0,2 ÷ 2,50 mm²

 

Operating temperature range:  -20 ÷ +60℃

 

Operating position:  free

 

Casing mounting:  TH35 rail (acc. to EN 60715)

 

Casing protection degree: IP20 (EN 60529)

 

Protection class: II

 

Overvoltage category:  II

 

Pollution degree:  2

 

Dimensions:  double modular (35 mm) 90 x 35 x 66 mm

 

Weight:  0,17 kg

 

Reference standard:  EN 60730-1; EN 60730-2-7,

 

  EN 61000-4-2,3,4,5,6,11

APPEARANCE**

LCD

Relay output terminals 
(12, 11, 14)

Control push buttons

External memory*

Input (release) terminals:

(IN, IN, IN, IN)

Input (supply) terminals:
(A1, A2)

Daytime / Night time

Winter time

Manual mode

Automatic mode

Day of the week

Relay mode

Information field / date

Current time (hh:mm:ss)

The symbol means selective collecting of 

electrical and electronic equipment.  

It is forbidden to put the used equipment 

together with other waste.

DESCRIPTION

MAIN MENU

STORAGE MODE

•  • The ZCM-32 programmers have a ‘storage mode’ default setting to protect the battery during storage.

•  • During battery backup operation, the first programmer activation is realised by means of pressing the ( ) button shortly which causes the storage mode is 

changed, next it is required to set the date and time.

•  • During rated voltage operation, the first programmer activation is realised by setting the time and date.

•  • The programmer can be readjusted to the storage mode by means of carrying out a device reset

•  - in order to do it press the ( ) and ( ) buttons simultaneously for a shorter time in the main menu.

Description of elements and messages displayed

Description of buttons

   

• in the main window - enter the automatic mode;

   

• in other windows – go up one level without saving the entered data; 

   

• in the main window – enter the manual mode or change the relay mode if the clock is in the manual mode;

   

• in other windows - go up one level without saving the entered data;

 

  • in the main window –enter the main menu;

   

• in other windows – enter the submenu or confirm the settings;

 

  • switching between windows / menu options or increasing /decreasing the pre-set parameters;

 

  

• right cursor ( ) in the main menu – sunrise and sunset time display.

Press OK to enter from the main menu to the 

menu; use cursors ( ) to move in the menu.  

It is possible to enter the main menu again by 

pressing the ( ) or ( ) button. From the main 

window you can also enter windows displaying 

the calculated sunrise/sunset time by pressing 

the ( ) cursor. Return is automatic after 10 s.

  Function Description

 

 

NIGHT BREAK SETTING

 

 

SUNRISE / SUNSET TIME CORRECTION SETTING

 

 

CURRENT TIME SETTING

 

 

CURRENT DATE SETTING

 

 

SUMMER / WINTER TIME SETTING

 

  GEOGRAPHICAL POSITION AND TIME ZONE SETTING

 

 

EXTERNAL INPUT SETTING

 

 

EXTERNAL MEMORY SETTING**

 

 

CALCULATED SUNRISE TIME

 

 

CALCULATED SUNSET TIME

** 

 

- days of the week

 - relay mode

 - automatic mode

 - manual mode

  - winter time

 - summer time

 - external input 

 - day

- year

 - night break setting

 - time correction setting

 - current time setting and summer / winter time change

 - current date setting

 - geographical position setting

 - external input setting

 - external memory operation **   

 - write to external memory **

 - read from external memory **

 - external memory usage**

 - reading / saving error**

 / 

 - sunrise / sunset time

 / 

 - latitude / longitude

 - automatic, 

 - user

 

 - switched on /switched off

OPERATION MODE CHANGE (AUTOMATIC, MANUAL)

,   i    Before changing the operation mode select channel (

) or (

) in the main menu 

by means of the (  ) cursor. 

 MODE CHANGE INTO MANUAL - f the system is in the main window and the automatic mode

 is active, press the ( ) button to change the system into the manual mode with a simultaneo-

us change of the relay mode;

 i   Subsequent pressing of the ( ) button causes the relay switches to the opposite mode, but 

the operation mode does not change;

 MODE CHANGE INTO AUTOMATIC - if the system is in the main menu and the manual mode 

is active, press the ( ) button to change the system into the automatic mode with a simulta-

neous change of the relay mode;

 and   Subsequent pressing 

of  the  ( )  button  causes  the 

relay switches to the opposite 

mode, but the operation mode 

does not change;

Отзывы: