, e-mail: [email protected]

plik: inst_ext_en_zcm-31_31PU | modyfikacja: 06.04.2016

DESCRIPTION

MAIN MENU

STORAGE MODE

APPEARANCE**

OPERATION MODE CHANGE (AUTOMATIC, MANUAL)

•  • The ZCM-31 programmers have a ‘storage mode’ default setting to protect the battery during storage.

•  • During battery backup operation, the first programmer activation is realised by means of pressing the ( ) button shortly which causes the storage mode is 

changed, next it is required to set the date and time.

•  • During rated voltage operation, the first programmer activation is realised by setting the time and date.

•  • The programmer can be readjusted to the storage mode by means of carrying out a device reset

•  - in order to do it press the ( ) and ( ) buttons simultaneously for a shorter time in the main menu.

Description of elements and messages displayed

Description of buttons

   

• in the main window - enter the automatic mode;

   

• in other windows – go up one level without saving the entered data; 

   

• in the main window – enter the manual mode or change the relay mode if the clock is in the manual mode;

   

• in other windows - go up one level without saving the entered data;

 

  • in the main window –enter the main menu;

   

• in other windows – enter the submenu or confirm the settings;

 

  • switching between windows / menu options or increasing /decreasing the pre-set parameters;

 

  

• right cursor ( ) in the main menu – sunrise and sunset time display.

Press OK to enter from the main menu to the 

menu; use cursors ( ) to move in the menu.  

It is possible to enter the main menu again by 

pressing the ( ) or ( ) button. From the main 

window you can also enter windows displaying 

the calculated sunrise/sunset time by pressing 

the ( ) cursor. Return is automatic after 10 s.

  Function Description

 

 

NIGHT BREAK SETTING

 

 

SUNRISE / SUNSET TIME CORRECTION SETTING

 

 

CURRENT TIME SETTING

 

 

CURRENT DATE SETTING

 

 

SUMMER / WINTER TIME SETTING

 

  GEOGRAPHICAL POSITION AND TIME ZONE SETTING

 

 

EXTERNAL INPUT SETTING

 

 

EXTERNAL MEMORY SETTING**

 

 

CALCULATED SUNRISE TIME

 

 

CALCULATED SUNSET TIME

FEATURES

TECHNICAL DATA 

DESCRIPTION

 

 

Input (supply) terminals: A1, A2

 

Nominal supply voltage: ZCM-31: 230 V AC~(-15 ÷ +10 %)

 

 ZCM-31P/U: 24 ÷ 250V AC, 30 ÷ 300 V DC

 

Nominal frequency: 50 / 60 Hz

 

Nominal power consumption:  ZCM-31: 1,5 W / 16 VA – stand-by 

 

 / switched on relay

 

 ZCM-31P/U: 0,8 W / 1,4 VA – stand-by

  

ZCM-31P/U: 1,5 W / 2,9 VA - switched on relay

 

Number of channels:  1

 

Programme:  astronomical (official dawn and dusk)

 

Operation modes:  manual, automatic

 

Summer/winter time change:  automatic, manual 

 

LCD backlight colour:  amber

 

External input:  yes

 

Cooperation with external memory:  ZCM-31: no

 

 ZCM-31P/U: yes

 

Time measuring accuracy:  max. ± 1 s / 24 h for 25°C

 

Clock battery backup:  3 years

 

Programme battery backup:  10 years

 

Input (release) terminals:  IN, IN, IN, IN

 

Output (load) terminals:  11, 12, 14

 

Relay contact parameters:  1 NO / NC 16 A / 250 V AC1 4000 VA 

 

Number of connection terminals:  12

 

Cross-section of connection cables:  0,2 ÷ 2,50 mm²

 

Operating temperature range:  -20 ÷ +60°C

 

Operating position:  free

 

Casing mounting:  TH35 rail (acc. to EN 60715)

 

Casing protection degree: IP20 (EN 60529)

 

Protection class: II

 

Overvoltage category:  II

 

Pollution degree:  2

 

Dimensions:  double modular (35 mm) 90 x 35 x 66 mm

 

Weight:  0,17 kg

 

Reference standard:  EN 60730-1; EN 60730-2-7, 

 

 EN 61000-4-2,3,4,5,6,11

● control depending on current time in the 

astronomical cycle,

● double modular casing with a protective 

cover,

● IN control input,

● LCD with backlight,

● mounting on a TH35 rail.

ZCM-31 digital time programmers are 

used to realize time functions in automa-

tion and control systems. Switching on / 

switching off the device is related to sun-

set and sunrise (official dawn and dusk). 

The following information on geographic 

coordinates of the clock’s installation 

place, current date, and time difference 

with regard to the universal time (GMT) 

is used to calculate the time of sunrise 

and sunset. The system calculates the 

so-called official time of sunrise and sun-

set and this is the phase when the upper 

edge of the Sun touches the horizon. Ad-

ditionally, the system has the function of 

a programmable night break and a pos-

sibility to change the calculated sunrise/

sunset time in the range of ±120 min. 

The device casing construction allows 

the system to be installed on a TH35 rail 

and additionally the casing can be sealed. 

The system structure guarantees battery 

backup of the settings in case of power 

supply failure.

CAUTION:

To protect the programmer’s battery 

during storage time, the ZCM-31 series 

has a ‘storage mode’ default setting 

with a minimum current consumption.

The device is designed for sin-

gle-phase installation and must be in-

stalled in accordance with standards 

valid in a particular country. The de-

vice should be connected according 

to the details included in this manual instruction. 

Installation, connection and control should be 

carried out by a qualified electrician staff, who 

act in accordance with the service manual and 

the device functions. In case of casing disman-

tling, the guarantee is lost and an electric shock 

may occur. Before installation make sure the 

connection cables are not under voltage. Im-

proper transport, storage, and use of the device 

influence its wrong functioning. It is not advis-

able to install the device in the following cas-

es:  if any device part is missing or the device 

is damaged or deformed. In case of improper 

functioning of the device contact the producer.

The symbol means selective collecting of elec 

trical and electronic equipment. It is forbidden to 

put the used equipment together with other waste.

LCD

Relay output terminals 
(12, 11, 14)

Control push buttons

External memory*

Input (release) terminals:

(IN, IN, IN, IN)

Input (supply) terminals:
(A1, A2)

Daytime / Night time

Winter time

Manual mode

Automatic mode

Day of the week

Relay mode

Information field / date

Current time (hh:mm:ss)

The symbol means selective collecting of 

electrical and electronic equipment.  

It is forbidden to put the used equipment 

together with other waste.

CAUTION! 

* not applicable to ZCM-31

** applicable to ZCM-31P/U

* not applicable to ZCM-31

** applicable to ZCM-31P/U

** 

 

- days of the week

 - relay mode

 - automatic mode

 - manual mode

  - winter time

 - summer time

 - external input 

 - day

- year

 - night break setting

 - time correction setting

 - current time setting and summer / winter time change

 - current date setting

 - geographical position setting

 - external input setting

 - external memory operation **   

 - write to external memory **

 - read from external memory **

 - external memory usage**

 - reading / saving error**

 / 

 - sunrise / sunset time

 / 

 - latitude / longitude

 - automatic, 

 - user

 

 - switched on /switched off

 MODE CHANGE INTO MANUAL - if the system is in the main window and the automatic mode ( ) is active, 

press the ( ) button to change the system into the manual mode with a simultaneous change of the relay 

mode;

   Subsequent pressing of the ( ) button causes the relay switches to the opposite mode, but the operation 

mode does not change;

    MODE CHANGE INTO AUTOMATIC - if the system is in the main menu and the manual mode is active, 

press the ( ) button to change the system into the automatic mode with a simultaneous change of the 

relay mode.