ZCM-12, ZCM-12/U TIME PROGRAMMER
WEEK’S, DOUBLE CHANNEL
INSTRUCTION MANUAL
Zak
ł
ad Mechaniki i Elektroniki
ZAMEL
sp.j.
J.W. Dzida, K.
Ł
odzi
ń
ska
ul. Zielona 27, 43-200 Pszczyna, Poland
Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04
www.zamelcet.com
, e-mail: [email protected]
APPEARANCE
FEATURES
TECHNICAL DATA
DESCRIPTION
ZCM-12
Power supply terminals: A1, A2
Input rated voltage:
ZCM-12: 230 V AC
~
(-15 ÷ +10 %)
ZCM-12/U: 24 ÷ 250 V AC, 30 ÷ 300 V DC
Nominal frequency: 50 / 60 Hz
Rated power consumption: 2 W / 14 VA
Number of channels: 2
Program quantity: 400 (100 On/Off pairs per channel)
Program: daily, week’s
Operating modes: manual, automatic, random, impulse
Change of season summer/ winter: automatic, manual
Colour of LCD panel lighting: amber
Input: 2
Accuracy of time measurement: max ±1 s / 24 h at temp. 25 °C
Time of clock maintenance: 3 years
Time of programme maintenance: 10 years
Clamps of release system: IN1, IN1, IN2, IN2
Receiver input (supply) terminals: 11, 12, 14, 21, 22, 24
Output relay parameters: 2 NO/NC-16 A/250 V AC1 4000 VA
Number of terminal clamps: 12
Section of connecting cables: 0,2 ÷ 2,50 mm
2
Ambient temperature range: -20 ÷ +60
o
C
Operating position: freely
Mounting: rail TH 35 (PN-EN 60715)
Protection degree: IP20 (PN-EN 60529)
Protection level: II
Overvoltage category: II
Pollution degree: 2
Dimensions: double-modular (35 mm) 90x35x66 mm
Weight: 0,140 kg
Reference standards: PN-EN 60730-1; PN-EN 60730-2-7
PN-EN 61000-4-2,3,4,5,6,11
●
Week’s cycle control in dependence
of the current hour,
●
Double-module casing with a protec-
tion flap,
●
Random op mode, additional IN con-
trol inputs,
●
Double-channel version,
●
Many programs,
●
LCD display illumination,
●
Mounted on TH 35 rail.
The ZCM-12 control timers are de-
signed for time functions execution in
automatics and control systems. The
week’s programmer controls the output
relay in dependence of program settings
(day, hour). The device is
fi
tted with some
additional functions, among other things
the random function that is used for the
operating mode changing by means of
an external push button. It is possible to
mount the device on TH 35 rail and seal
it if needed.
In case of power supply
malfunction the unit battery sustain
enables all settings saving and main-
taining.
CAUTION:
Before installing
the device in the
switchboard
or starting the
system operation
in order to pro-
gramme it, the bat-
tery security sepa-
rator should be
removed against
discharging.
The device is designed for sin-
gle-phase installation and must
be installed in accordance with
standards valid in a particular
country. The device should be
connected according to the de-
tails included in this operating
manual. Installation, connection and control
should be carried out by a quali
fi
ed electrician
staff, who act in accordance with the service
manual and the device functions. Disassem-
bling of the device is equal with a loss of gu-
arantee and can cause electric shock. Before
installation make sure the connection cables
are not under voltage. The cruciform head
screwdriver 3,5 mm should be used to instal
the device. Improper transport, storage, and
use of the device in
fl
uence its wrong functio-
ning. It is not advisable to instal the device in
the following cases: if any device part is mis-
sing or the device is damaged or deformed.
In case of improper functioning of the device
contact the producer.
CAUTION
Relay output terminals
(12, 11, 14, 24, 21, 22)
Control buttons
Trigger terminals
(IN1, IN1, IN2, IN2)
Display
Power terminals
(A1, A2)
VER. 001_21.09.2009
IN active input
Impulse mode active
Winter/summer time
Random mode
Manual mode
Automatic mode
Week’s day
Relay state
Info
fi
eld
Current time (gg:mm:ss)
The symbol means selective collecting
of electrical and electronical equipment.
It is forbidden to put the used equipment
together with other waste
DESCRIPTION
MAIN MENU
DATE SETTING
- Current date setting; entry after pressing OK;
YEAR - choose adequate year with cursors
con
fi
rm with OK, range of
years: 2000÷2099;
MONTH - choose month with cursors
con
fi
rm with OK;
DAY - choose day with cursors
con
fi
rm with OK; the system has a protec-
tion against introducing incorrect parameter of a day for a given month (it
takes into account leap years and it automatically calculates the day of the
week on the basis of an arranged date);
Con
fi
rmation causes movement to a date setting window and set-up of cur-
rent summer/ winter time - if the option
is arranged.
It is possible to exit every submenu window in any moment without sav-
ing settings by pressing the button or .
Description of elements and messages displayed
- days of week
- day,
- year
- transmitter’s status
- program setting
- automatic mode
- current time setting and summer/winter time shift
- manual mode
- current date setting
- random mode
- random mode setting
- impulse mode
- extenal input setting
- external input
- impulse mode setting
- winter time
- automatic,
- user
- summer time
- channels
- on/off
Button description
• in the main window – the automatic mode enter or relay state changeover, if the timer already in the automatic
mode;
• in the main window (3 seconds) – the random mode enter / exit;
• in the random mode – randomizing active/inactive manual toggle;
• the other windows – exit to a higher level without changes saving;
• in the main window – the manual mode enter or the relay state changeover, if the timer already in the manual mode;
• in the random mode – the relay state changeover and randomizing switch-OFF;
• the other windows - exit to a higher level without changes saving;
• in the main window – the main menu enter;
• the other windows – a submenu enter or setting acknowledgement;
• window/option toggle or set value increase/decrease.
Menu enter by pressing OK;
menu items scrolling by means of cursors
.
Function Description
PROGRAM SETTING
CURRENT
TIME
SETTING
CURRENT DATE SETTING
WINTER / SUMMER TIME SETTING
EXTERNAL INPUT SETTING
IMPULSE MODE SETTING
RANDOM MODE SETTING
ZCM - 12
TIME SETTING
WINTER / SUMMER TIME SETTING
OPERATING MODE CHANGE (AUTOMATIC, MANUAL, RANDOM)
- setting the current clock time; entry after pressing
OK;
HOUR- choose adequate hour with cursor
which you can
set in 1-24 or 1-12 (AM) and 1-12 (PM)format; con
fi
rm
with OK;
MINUTES - choose adequate parameter of minutes with cur-
sors
con
fi
rm with OK;
Con
fi
rmation of the parameter of minutes causes simultane-
ous nulli
fi
cation of the parameter of seconds and movement
to the window of time setting.
It is possible to exit every submenu window in any moment
without saving settings by pressing the button or .
- winter/summer time toggle mode selection:
- automatic time changing on the last March Sunday, at 2:00
into summer time and on the last October Sunday, at 3:00
into winter time,
- winter/summer timer toggle manual,
by user; option entering after pressing OK;
MODE SETTING - with
select
or
acknowl-
edge with OK; after selecting
, winter/summer time will
be toggled automatically; after selecting
mode you will
enter the next window;
With
select winter/summer, where is winter time, -
summer time; if the time icon is changed, the timer will cor-
rect the current time appropriately; acknowledge by pressing
OK;
After time mode selecting winter/summer time change win-
dow will be open.
Before the op mode changing it is necessary, in the
main window, to select with the cursors
channel
or
.
MANUAL OP MODE TOGGLE - if the main window is open
and the timer is in the automatic mode pressing the key
will force the unit to toggle into the manual mode and the
relay state changeover;
Successive key pressing will force the relay state
changeover without the op mode changing;
AUTOMATIC MODE TOGGLE – if the main window is open
and the timer is in the manual mode pressing the key will
force the unit to toggle into the auromatic mode and the relay
state changeover;
Successive key pressing will force the relay state
changeover without the op mode changing;
RANDOM MODE TOGGLE - in order to enter the random
mode it is necessary to press and hold key for
3 secs
;
Pressing the key forces the relay state changeover; in
order to exit the random mode it is necessary to press the
key .