YZ Systems Milton Roy • 201 Ivyland Road • Ivyland, Pennsylvania • USA • 18974 • P: 281.362.6500 • www.yzsystems.com
Page 7
NJEX 7300G ver.08-2018
Section 2: System Installation
'A'
8-10 AWG
Grounding Rod
Depth of
4'-0" Min.
FRONT VIEW
SIDE VIEW
BACK VIEW
'B'
'C'
Standard System Mounting
Figure 5
1. Bolt down the system enclosure to a concrete
slab using the mounting holes (9/16”) provided in
the bottom of each leg of the enclosure. Recom-
mended bolt/stud sizes for mounting the enclosure
is 1/2”.
2. In order to satisfy NEC requirements you
must connect a ground wire from the ground-
ing lug located on the enclosure leg to a prop-
erly installed ground rod, located adjacent to
the system enclosure. *Resistance to ground
must be less than 1 Ohm. To assure proper
system operation this ground should not be a
shared ground with any other equipment.
TABLE
A
B
C
SINGLE
20-3/4”
20-1/4”
9”
DUAL
40-1/4”
39-1/2”
9”
Содержание NJEX 7300G
Страница 1: ...NJEX 7300G N A T U R A L G A S O D O R I Z A T I O N S Y S T E M ...
Страница 2: ......
Страница 3: ...The NJEX 7300G Instruction Operating Manual Version 08 2018 ...
Страница 4: ......
Страница 10: ......