background image

 

 

13 

3.2  Complete Parameter Table 

 

The parameters can be divided to 8 groups including alarm, control, input, output, communication, system, 

setpoint and field parameter definition.    They are listed as below in sequence:   

Code 

Name 

Description 

Setting 

Range 

HIAL 

High 

limit 

alarm 

Alarm on when PV (Process Value) >HIAL; alarm off when PV<HIAL-AHYS 
Alarm output action can be defined by parameter AOP. 

-9990

+30000 

units 

LoAL 

Low limit alarm 

Alarm on when PV<LoAL; alarm off when PV>LoAL+AHYS 

HdAL 

Deviation  high 
alarm 

Alarm on when PV-SV>HdAL; alarm off when PV-SV<HdAL-AHYS 

LdAL 

Deviation  low 
alarm 

Alarm on when PV-SV<LdAL; alarm off when PV-SV>LdAL+AHYS 
HdAL  and  LdAL  can  also  be  used  as  high  limit  and  low  limit  alarms  when  needed.   
(Refer to the description of parameter AF) 

AHYS 

Alarm 
hysteresis 

Avoid frequent alarm on-off action because of the fluctuation of PV 

0

2000 

units 

AdIS 

Alarm display 

oFF : don’t display AdIS in the lower display window when alarming; 
on : alternately display AdIS in the lower display window when alarming. 

oFF 

on 

AOP 

Alarm 

output 

allocation 

From right side to left side, the first, second,  third and fourth digit of AOP individually 
indicate  the  alarm  output  terminal  of  HIAL,  LoAL,  HdAL,  and  LdAL.    0  shows  no 
output.    1,2,3 or 4 indicates alarm outputted to AL1, AL2, AU1 or AU2.    For example, 

AOP    =        3                  3                  0                1     
                         

            LoAL          HdAL          LoAL          HIAL 

It  shows  that  HIAL  is  sent  to  AL1,  LoAL  has  no  output,  HdAL  and  LdAL  are  sent  to 
AU1.     
Note  1:  When  AUX  is  used  as  auxiliary  output  in  bidirectional  (heating/refrigerating) 
control, allocating alarm to AU1 and AU2 does no effect. 
Note 2: Installing L3 dual relay output module in ALM or AUX can implement AL2 or 
AU2 alarm. 

0

4444 

CtrL 

Control mode 

onoF: on-off control.    For situation not requiring high precision; 
APId: advanced artificial intelligence PID control.    Recommended 
nPId:  standard  PID  algorithm  with  anti

–integral-saturation  function  (no  integral  when 

PV-SV > proportional band); 
POP: output PV.    The instrument works as a temperature retransmitter. 
SOP: output SV.    The instrument works as a set current output. 

onoF 

APId 

nPId 
POP 
SOP 

Act 

Acting method 

rE:  Reverse  acting.    Increase  in  measured  variable  causes  an  decrease  in  the 
output, such as heating control. 
dr:  Direct  acting.    Increase  in  measured  variable  causes  an  increase  in  the  output, 
such as refrigerating control. 
rEbA:  Reverse  acting  with  low  limit  alarm  and  deviation  low  alarm  blocking  at  the 
beginning of power on. 
drbA:  Direct  acting  with  high  limit  alarm  and  deviation  high  alarm  blocking  at  the 
beginning of power on. 

rE 

dr 

rEbA 

drbA 

A-M 

Auto/Manual 
Control  Mode 
Selection 

MAn: Manual control mode.    Manually adjust output value of OUTP. 
Auto: Auto control mode.    The instrument calculate and control the output value. 
FMAn: Fixed in manual control mode. Forbid switching to auto-mode by short-cut keys 
from panel. 
FAut: Fixed in auto control mode. Forbid switching to manual mode by short-cut keys 
from panel.   

MAn 
Auto 

FMAn 

FAut 

At 

auto tuning 

oFF: Auto tuning function is disable 
on: Active auto turning function to calculate the values of parameters P, I, d and CtI.   
After auto tuning is accomplished, “At” will be automatically changed to oFF. 
FoFF: Auto tuning is disabled, and activating auto tuning from basic display status is 
forbidden. 

 

Proportional 
band 

Proportional  band  in  PID  and  APID  control.    Instead  of  percentage  of  the 
measurement range, the unit is the same as PV. 
Generally, optimal P, I, D and CtI can be obtained by auto tuning.    They can also be 
manually input if you already know the correct values. 

10

9999 

units 

Time 

of 

Integral 

No integral effect when I=0 

0

9999 

seconds 

Time 

of 

Derivative 

No derivative effect when d=0 

0

999.9 

seconds 

CtI 

Control period 

Small value improves control accuracy.   
For SSR, thyristor or linear current output, generally 0.5 to 3 seconds. 
For Relay output or in a heating/refrigerating dual output control system, generally 15 
to  40  seconds,  because  small  value  will  cause  the  frequent  on-off  action  of 
mechanical switch or frequent heating/refrigerating switch, and shorten its service life.   

0.5

120.0 

seconds 

Содержание AI-519

Страница 1: ...ls of temperature pressure flow level humidity etc CONTENTS 1 SUMMARY 1 1 1 MAIN FEATURES 1 1 2 ORDERING CODE DEFINITION 1 1 3 TECHNICAL SPECIFICATION 4 1 4 REAR TERMINAL LAYOUT AND WIRING 6 2 DISPLAY...

Страница 2: ...nge of temperature ISO9001 and CE certified achieving world class level of quality anti interference ability and safety POINTS TO NOTE Always adjust parameters according to input output type and funct...

Страница 3: ...output or SV PV retransmission L1 Large capacity large size normal open relay output module Capacity 250VAC 2A L2 Small capacity small size normal open normal close relay output module Capacity 250VA...

Страница 4: ...ace or install modules by themselves when needed When replacing a module you should pull the controller out of the housing at first insert a small flat tip screwdriver into the opening between the ori...

Страница 5: ...can be chosen Calibration The instrument applies the technology of automatic zero and digital calibration and is free of maintenance If the error exceeds certain range generally cleaning and drying t...

Страница 6: ...power module Linear current output 0 20mA or 4 20mA Output voltage 11V maximum load resistance 500ohm output precision 0 2 FS Electromagnetic compatibility EMC 4KV 5KHz according to IEC61000 4 4 4KV a...

Страница 7: ...ignal can be converted to 1 5V voltage signal by connecting a 250 ohm resistor and input from terminals 11 and 12 3 S S1 or S4 module can be installed in COMM slot for communication If relay TRIAC no...

Страница 8: ...odule with parameter bAud 1 provides MIO on off input simulation SP1 SP2 The external switch should be connected to terminal 3 and 5 Wiring diagram of D6 size instruments 48 48mm 1 Linear voltage of 5...

Страница 9: ...struments 22 5 x 100mm 1 Input 0 5V 1 5V input from 12 11 500mV below input from 10 11 4 20mA with 250ohm shunt resistor converted to 1 5V input from 12 11 2 Fixed with one channel alarm and communica...

Страница 10: ...N4001 Load Thyristor trigger output SCR X2 5 500A BX BX Capacitor Resistor Absorber Circuit Varistor G1 G2 G1 G2 ZNR ZNR V V 100 240VAC TRIAC 5 500A Capacitor Resistor Absorber Circuit Varistor SCR Po...

Страница 11: ...the thermocouple or RTD circuit is break or input specification sets wrong the upper display window will alternately display orAL and the high limit or the low limit of PV and the instrument will aut...

Страница 12: ...password and then press can access System Parameter Table Setpoint Output Magnitude Switch In the basic display status pressing can switch lower display window between displaying setpoint or output m...

Страница 13: ...Generally the smaller the value of CHYS the higher is the precision of auto tuning But the value of CHYS parameter should be large enough to prevent the instrument from error action around setpoint du...

Страница 14: ...utput PV The instrument works as a temperature retransmitter SOP output SV The instrument works as a set current output onoF APId nPId POP SOP Act Acting method rE Reverse acting Increase in measured...

Страница 15: ...t value or corresponding parameter value may be larger than 9999 please avoid choosing 0 but 0 000 instead The display value will become 00 00 when the value is larger than 9999 0 0 0 0 00 0 000 ScL S...

Страница 16: ...he impulse current of induction load CtI 0 5 second and OPrt 5 second 0 3600 second OEF Work range of OPH When PV OEF the upper limit of OUTP is OPL when PV OEF the upper limit of OUTP is 100 For exam...

Страница 17: ...tion are satisfied the instrument should alarm but there is no problem in the system Contrarily in an refrigerating system the unnecessary high limit or deviation high limit alarm may occur at the beg...

Отзывы: