background image

 

 

11 

 

2.3 

Parameter Setting Flow Chart

 

2.4 

Operation Description

 

Parameter Setting 

In  basic display  status,  press 

  and  hold  for  about  2 seconds  can  access Field  Parameter  Table.    Pressing 

 

can go to the next parameter; pressing 

 

  or 

 

  can modify a parameter.    Press 

to decrease the data. 

Press 

 

  to  increase the data. The  decimal  place dot flashes where the data is  changing, looking like a mouse 

cursor. Press the button and hold, the speed of data change will go faster, and going further faster along with the 

shift  of  cursor. Press 

 

  to  direct  move  the  cursor. 

Press and hold 

 

  can return to the preceding parameter. The 

parameter  will  be  saved.  Press 

 

  (don't  release)  and  then  press 

  key  simultaneously  can  escape  from  the 

parameter table. The parameter will be saved. The instrument will escape auomatically from the parameter table if no key 

is pressed within 25 seconds, and the change of the last parameter will not be saved.   

In  Field  Parameter  Table,  press 

  till  the  last  field  parameter  Loc  appears.    Setting  Loc=password  and  then  press 

  can access System Parameter Table.   

 

Setpoint / Output Magnitude Switch

 

In  the  basic  display  status,  pressing 

  can  switch  lower  display  window  between  displaying  setpoint  or  output 

magnitude. If the instrument is in manual operating mode, even the lower display window is switched to setpoint display, it 

will automatically return to output magnitude display after a period of time. 

 

Setpoint (SV) Setting 

I

f the parameter lock “Loc” isn't locked, we can set setpoint (SV) by pressing 

 

,

  or 

 

. The range of setpoint is 

between the parameter SPL and SPH. 

 

Auto / Manual Control Mode Switch (A/M) 

When  output  magnitude  is  displayed  in  lower  display  window,  pressing  AT  key  (

 

)  can  switch  between  auto-control 

and  manual  control  without  bumping.  If  the  instrument  is  in  manual  control  mode  and  the  lower  display  window  is 

Auto Tuning 

Parameter 

AT 

High Limit 

Alarm HIAL 

Process Value   

Setpoint 

Parameter Lock 

Loc 

Run   

Auto Tuning 

 

Auto Tuning 

Parameter 

AT 

Output 60% 

Manual Mode

 

High Limit 

Alarm HIAL 

Output 60% 

Auto Mode

 

 

+

 

 

 

2 Sec

 

 

2Sec

 

 

 

 

 

Next   

Parameter 

 

2Sec

 

 

 

Next   

Parameter 

 

 

 

Password correct

 

 

 

 

+

 

 

 

Password   

incorrect 

 

 

 

2sec

 

 

2Sec

 

 

 

 

 

AT finished 

Power On 

B

as

ic 

D

ispl
ay S

tat

us

 

Field Parameters 

Entire Parameter Table 

 

 

 

 

 

2sec

 

 

 

 

 

 

 

 

 

Содержание AI-519

Страница 1: ...ls of temperature pressure flow level humidity etc CONTENTS 1 SUMMARY 1 1 1 MAIN FEATURES 1 1 2 ORDERING CODE DEFINITION 1 1 3 TECHNICAL SPECIFICATION 4 1 4 REAR TERMINAL LAYOUT AND WIRING 6 2 DISPLAY...

Страница 2: ...nge of temperature ISO9001 and CE certified achieving world class level of quality anti interference ability and safety POINTS TO NOTE Always adjust parameters according to input output type and funct...

Страница 3: ...output or SV PV retransmission L1 Large capacity large size normal open relay output module Capacity 250VAC 2A L2 Small capacity small size normal open normal close relay output module Capacity 250VA...

Страница 4: ...ace or install modules by themselves when needed When replacing a module you should pull the controller out of the housing at first insert a small flat tip screwdriver into the opening between the ori...

Страница 5: ...can be chosen Calibration The instrument applies the technology of automatic zero and digital calibration and is free of maintenance If the error exceeds certain range generally cleaning and drying t...

Страница 6: ...power module Linear current output 0 20mA or 4 20mA Output voltage 11V maximum load resistance 500ohm output precision 0 2 FS Electromagnetic compatibility EMC 4KV 5KHz according to IEC61000 4 4 4KV a...

Страница 7: ...ignal can be converted to 1 5V voltage signal by connecting a 250 ohm resistor and input from terminals 11 and 12 3 S S1 or S4 module can be installed in COMM slot for communication If relay TRIAC no...

Страница 8: ...odule with parameter bAud 1 provides MIO on off input simulation SP1 SP2 The external switch should be connected to terminal 3 and 5 Wiring diagram of D6 size instruments 48 48mm 1 Linear voltage of 5...

Страница 9: ...struments 22 5 x 100mm 1 Input 0 5V 1 5V input from 12 11 500mV below input from 10 11 4 20mA with 250ohm shunt resistor converted to 1 5V input from 12 11 2 Fixed with one channel alarm and communica...

Страница 10: ...N4001 Load Thyristor trigger output SCR X2 5 500A BX BX Capacitor Resistor Absorber Circuit Varistor G1 G2 G1 G2 ZNR ZNR V V 100 240VAC TRIAC 5 500A Capacitor Resistor Absorber Circuit Varistor SCR Po...

Страница 11: ...the thermocouple or RTD circuit is break or input specification sets wrong the upper display window will alternately display orAL and the high limit or the low limit of PV and the instrument will aut...

Страница 12: ...password and then press can access System Parameter Table Setpoint Output Magnitude Switch In the basic display status pressing can switch lower display window between displaying setpoint or output m...

Страница 13: ...Generally the smaller the value of CHYS the higher is the precision of auto tuning But the value of CHYS parameter should be large enough to prevent the instrument from error action around setpoint du...

Страница 14: ...utput PV The instrument works as a temperature retransmitter SOP output SV The instrument works as a set current output onoF APId nPId POP SOP Act Acting method rE Reverse acting Increase in measured...

Страница 15: ...t value or corresponding parameter value may be larger than 9999 please avoid choosing 0 but 0 000 instead The display value will become 00 00 when the value is larger than 9999 0 0 0 0 00 0 000 ScL S...

Страница 16: ...he impulse current of induction load CtI 0 5 second and OPrt 5 second 0 3600 second OEF Work range of OPH When PV OEF the upper limit of OUTP is OPL when PV OEF the upper limit of OUTP is 100 For exam...

Страница 17: ...tion are satisfied the instrument should alarm but there is no problem in the system Contrarily in an refrigerating system the unnecessary high limit or deviation high limit alarm may occur at the beg...

Отзывы: