ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER

AI-508/AI-509 

(V7.5) User Manual

GENERAL

AI-508/509, an economical and easy operated model of Yudian artificial intelligence 
industry controller, is specially designed for use in the industries of plastic machinery, 
food machinery, packaging machinery, baking machinery and environmental testing 

equipment.  It features:

Application of artificial intelligence control algorithm with auto tuning function, 

avoiding the overshoot problem of standard PID algorithm and achieving precise 

control. 

Multiple thermocouples and RTDs are selectable.  Integrated non-linear graduation 

tables, digital calibration and auto zero technology, and achieving accurate and 
stable measurement.

Advanced modular structure, conveniently providing various outputs options, and 

making quick delivery and easy maintenance.

High quality and performance hardware design, using high performance tantalum 

capacitor or ceramic capacitor.  Compared to competing models, it consumes less 
electricity, experiences less temperature shifting, provides higher stability and 
reliability and can work in a wider range of temperature. 

ISO9001 certification and CE certified, achieving world class level of quality, anti-

interference ability and safety.

MODEL CODE SYMBOL

The model code of AI-508/509 is made up of 5 parts, for example: 

      

                            AI-508/509      A     G     L2     L2                                   
                                    

            

    

     

     

              

  

shows the basic function of instrument: 

AI-508 Economical artificial Intelligence Temperature Controller 0.3%FS 

±

 1

AI-509 Economical artificial Intelligence Temperature Controller 0.3%FS 

±

 0.1

  

Shows the front panel dimension:

Size

Front Panel

width×height

Cut Out

width×height

Depth Behind

Mounting Surface

A

96×96mm

92×92mm

100mm

D

72×72mm

68×68mm

95mm

D2

48×48mm

45×45mm

95mm

E

48×96mm

45×92mm

100mm

F

96×48mm

92×45mm

100mm

  and 

 indicate the module installed in OUTP, ALM and AUX sockets. 

Allowed modules in each socket are as below:

                     

Allowed Type

Module Socket

N

L0

L1

L2

L3

G

W1 K1

K3

OUTP (main output)

ALM (Alarm)

 AUX (Auxiliary output)

N    (or none) no module installed
L0  Relay contact output module (Capacity: 2A/250VAC, only normal open 

terminal can absorb electrical spark), usually use for alarm

L1  Relay contact output module (Capacity: 2A/250VAC, only normal open 

terminal can absorb electrical spark), usually use for control

L2  Relay contact output module (Capacity: 1A/250VAC, small volume)
L3  Output module of dual normally open relay contact (Capacity: 2A/250VAC, 

support AL1 and AL2 alarm output)

G    SSR voltage output module (30mA/12DC) 
W1 TRIAC no contact normally open discrete output module, suitable for AC 

contactors up to 80A, and has low interference and long life.

K1 TRIAC zero crossing trigger output module.  One loop of output, suitable for 

single-phase power.

K3 Three phases TRIAC zero crossing trigger output module (can trigger triple 

of TRIAC,2 inversely parallel connected SCR or TRIAC power module of 

current 5-500A),will piug in OUPT slot and MIO slot at same time.

 Note 1: For instrument of dimension D2, because of  its limited volume, when L1 or 

L3 module is installed in AUX slot, L1 can’t be installed in OUPT slot, but 

L2, which is smaller, can be installed instead.

 Note 2: K3 can’t be installed in instrument with dimension D or D2. There isn’t 

ALM slot in D2 instruments. L3 module can’t be installed in ALM slot of 

instrument with dimension D.

TECHNICAL SPECIFICATION

Input type: 

K, S, R, E, J, N, Pt100 

Measurement range :

K(0~1300

),  S(0~1700

),  R(0~1600

),  E(0~1000

),  J(0~1200

),  

N(0~1300

),  Pt100(-200~800

)

Measurement accuracy :

 AI-508

0.3%FS±1

                                           

AI-509

0.3%FS±0.1

 

Temperature display resolution :

 AI-508

1

/

                                                       

AI-509

0.1

/

Control Mode: 

On-Off Control or Artificial Intelligence PID control with auto tuning.

Output mode (modularized) : 

L1  Relay contact output module (Normal open + normal close.  Capacity: 

2A/250VAC or 30VDC/2A)

L2  Relay contact output module (Capacity: 1A/250VAC, small volume)
G  SSR voltage output module ( 12VDC/30mA)
W1  TRIAC no contact normally open discrete output module (Capacity: 

100~240VAC/0.2A, instantaneous current 2A with time<20ms and repeat 
period>5s) 

K1  Thyristor zero crossing trigger output module (can trigger TRIAC, a pair of 

inversely parallel connected SCRs or SCR power module with current rating 
of 5-500A)

K3  Three-phase Thyristor zero crossing trigger output module (can trigger three 

phases of TRIAC, 2 inversely parallel connected SCRs or SCR power module 
of current 5-500A)

Alarm function : 

High limit/low limit, and deviation high/deviation low alarm.

Power supply : 

100-240VAC, -15%, +10% ;  50-60Hz

Power consumption:

 

3W

Ambient :

Temperature of -10~+60

/14-140

; humidity of 0~90RH%

 Reliability : 

repairing and returning rate 

 0.8% (according to the statistics data 

from 2003 to 2004.)

Electromagnetic compatibility (EMC) : 

IEC61000-4-4:  ±  4KV/5KHz; 

IEC61000-4-5: 4KV

FRONT PANEL AND OPERATION

 Upper display window, displays PV, or code of a parameter

 Lower display window, displays  SV, alarming code , or value of a parameter

 Setup key, for accessing parameter 

tables, and confirming change

 Data shift key, also for activating auto 

turning

 Data decrease key

 Date increase key

 Indicator lamps: (OP1, AL1, AL2, 

AU1and AU2 indicate the I/O actions 
of the corresponding modules)

    Basal display status :

 When power 

on,  the  upper  display  window  of  the 
instrument shows the process value (PV). and the lower window shows the setpoint 
(SV).This status is called basic display status. When the input signal is out of the 
measurable range (for example, the thermocouple or RTD circuit is break, or input 
specification sets wrong), the upper display window will alternately display “orAL” 
and the high limit or the low limit of PV,  and the instrument will automatically stop 

output.

OPERATION DESCRIPTION

Setpoint Setting:

In basic display status,  if the parameter lock“Loc”isn't locked, we can set setpoint 
(SV) by pressing 

 

  / 

 

 or

 

 . Press 

 

  key to decrease the value,  

 

key to increase the value, and 

 

 key to move to the digit expected to 

modify. Keep pressing  

 

or 

 

 , the speed of increasing or decreasing value 

gets quick. The range of setpoint is between the parameter SPL and SPH.  The 
default range is 0~

400

.

Parameter Setting

In basal display status, Press

 

and hold for about 2 seconds can access Field 

Parameter Table.  Pressin 

 

can go to the next parameter;  pressing 

 

  / 

 

 

or

 

 can modify the ralue of a parameter.  Press and hold

 

can return to the 

preceding parameter. Press

 

 (don't release) and then press 

 

 simultaneously 

can escape from the parameter table. The instrument will escape automatically 
from the parameter table if no key is pressed within 25 seconds.Setting Loc=808 
and then press 

 

can access System Parameter Table.

Artificial Intelligence control and auto tuning

When AI PID control method is chosen (CtrL=APId),  the PID parameters can 
be obtained by running auto-tuning.  In basal display status, press 

 

 for 2 

seconds,  the "At" parameter will appear.  Press 

 

 to change the value of "At" 

from "oFF" to "on", then press 

 

 to active the auto-tuning process.  During 

auto tuning, the instrument executes on-off control.  After 2 cycles of on-off 
action, the instrument will obtain the values of PID parameter .  If you want to 
escape from auto tuning status, press and hold 

 

 for about 2 seconds until the 

"At" parameter appear again.  Change "At" from "on" to "oFF", press  

 

to 

confirm, then the auto tuning process will be cancelled.  

 Note 1:If the setpoint is different, the parameters obtained from auto-tuning are 