SECTION 6 - OPERATION
TABLE 28 -
LOAD LIMITING VALUES
PARAMETER
(X AXIS UNITS)
X POINT
Y POINT
Z POINT
MOTOR CURRENT (%FLA)
Active Current Limit Setting –
2% FLA
Active Current Limit Setting
Active Current Limit S
5% FLA
DISCHARGE PRESSURE
High Discharge Pressure
Cutout – 15 psig
High Discharge Pressure
Cutout – 15 psig
High Discharge Pressure
Cutout
EVAPORATOR PRESSURE
Low Evaporator Pressure
10 psig
Low Evaporator Pressure
5 psig
Low Evaporator Pressure
Cutout
VSD INTERNAL AMBIENT
TEMP
VSD Internal Ambient Cutout
– 3°F
VSD Internal Ambient Cutout
– 2°F
VSD Internal Ambient Cutout
VSD BASEPLATE TEMP
VSD Baseplate Temp – 8°F
VSD Baseplate Temp – 4°F
VSD Baseplate Temp
LEAVING CHILLED LIQUID
TEMPERATURE
(HEAT PUMP MODE ONLY)
Low Leaving Chilled Liquid
Temp Cutout – + 4°F
Low Leaving Chilled Liquid
Temp Cutout – +2°F
Low Leaving Chilled Liquid
Temp Cutout – +2°F
NOTE:
All of the controls above are active immediately at start-up.
•
Remote BAS Comms Reset
: Set the LCHLT
setpoint via the BAS COMMS. The control panel
will only accept a remote setpoint from the BAS,
if the control panel is in REMOTE CONTROL
mode (under OPTIONS). If the control panel is in
LOCAL CONTROL mode, the BAS setpoint will
be ignored, and the remote LCHLT setpoint is set
to the local setpoint. The minimum and maximum
allowable reset values will be the same as those
allowable programmable values for the local
setpoint. If these values are exceeded by the BAS,
the minimum or maximum value will be used.
•
Remote Analog Reset
: Set the remote LCHLT
setpoint via the REMOTE TEMPERATURE
RESET analog input. A zero signal input (0%)
equates to a 0°F (0°C) offset to the local setpoint.
A full scale signal input (100%) equates to a posi-
tive offset to the local setpoint equal to the pro-
grammable maximum REMOTE TEMP RESET.
The offset is linear and may be adjusted between
0% and 100% points. The maximum setpoint
allowed is the maximum programmable local
setpoint, which will be capped at this value, if the
calculated setpoint with temperature offset ex-
ceeds this value.
This input may be used either in LOCAL or RE-
MOTE CONTROL mode, which will only oper-
ate if enabled under the UNIT SETUP mode and
the OPTIONS key. The input will be ignored if
the REMOTE TEMP RESET is disabled un-
der the OPTIONS key, or if there are valid BAS
COMMS while in REMOTE CONTROL mode.
Pulldown Current Limit Setpoint
Set this setpoint under the PROGRAM key, which
is only active on start-up for the time defined by the
PULLDOWN CURRENT LIMIT TIME. After the run
time has exceeded this time, the PULLDOWN CUR-
RENT LIMIT setpoint is ignored.
This control is useful in limiting current pulldown de-
mand during peak usage periods where electric costs
are highest.
Limiting current may interfere with
capacity control, pulling down chilled
liquid temperatures on hot water starts,
and maintaining chilled liquid setpoints.
If there are questions about the following reset con-
trols, contact a Johnson Controls BAS representative
for details on BAS controls and capabilities.
Leaving Chilled Liquid Temperature (LCHLT)
Reset Control
The LCHLT RESET CONTROL is used to reset the ac-
tual LCHLT setpoint used in capacity control. Refer to
the three methods below to reset the LCHLT setpoint:
•
Local Cooling Reset:
Reprogram the local cool-
ing setpoint under the SETPOINTS key, which
is the value to which the unit will control the
LCHLT, if no other method is active.
REMOTE TEMPERATURE LIMIT RESET is
only possible if the option is enabled by select-
ing OPTIONS key, and programmable password
protected UNIT SETUP MODE from the factory.
Содержание YVWA
Страница 14: ...JOHNSON CONTROLS 14 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 64: ...JOHNSON CONTROLS 64 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 82: ...JOHNSON CONTROLS 82 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 130: ...JOHNSON CONTROLS 130 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 146: ...JOHNSON CONTROLS 146 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 152: ...JOHNSON CONTROLS 152 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 155: ...JOHNSON CONTROLS 155 NOTES...