SECTION 7 – UNIT CONTROLS
035-02550-xxx I/O Board
FIGURE 45 -
MICRO PANEL CONNECTIONS
LD14318
The table below shows the minimum, maximum, and
default values.
TABLE 19 -
MINIMUM, MAXIMUM AND DEFAULT VALUES
DESCRIPTION
MINIMUM
MAXIMUM
DEFAULT
DE MODIFIER ADDRESS
-1
41943
-1
DE MODIFIER OFFSET
-1
99
-1
P1 BAUD RATE
1200
76800
4800
1200, 4800, 9600, 19200, 38400, 76800, AUTO SELECTABLE
P2 BAUD RATE
1200
57600
1200
1200, 4800, 9600, 19200, 38400, 57600 SELECTABLE
P1, P2 MANUAL Mac
ADDRESS
-1
127
-1
P1, P2 PARITY
NONE
IGNORE
NONE
NONE, EVEN, ODD, IGNORE SELECTABLE
P1 PROTOCOL
BACNET
API
BACNET
BACNET, API SELECTABLE
P2 PROTOCOL
TERMINAL
MODBUS CLIENT
API
TERMINAL, MODBUS IO, MODBUS SERVER, API, MODBUS CLIENT SELECTABLE
P1, P2 STOP BITS
1
2
1
RESET REAL TIME ERROR
NO
YES
NO
Содержание YLAA0041
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 72 ICOM6 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 32: ...JOHNSON CONTROLS 32 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 110: ...JOHNSON CONTROLS 110 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 122: ...JOHNSON CONTROLS 122 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 174: ...JOHNSON CONTROLS 174 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...