FORM 160.75-EG1 (519)
JOHNSON CONTROLS
53
Application Data (Cont'd)
TABLE 6
- FLOODED EVAPORATOR WATER FLOW RATE LIMITS GPM (L/S) – BASED UPON STANDARD
TUBES @ DESIGN FULL LOAD CONDITIONS (CONT'D)
FLOODED EVAPORATORS
CONDENSER
MODEL
1 PASS
2 PASS
3 PASS
MODEL
1 PASS
2 PASS
3 PASS
MIN
MAX
MIN
MAX
MIN
MAX
MIN
MAX
MIN
MAX
MIN
MAX
XR
5272
(333)
21087
(1330)
2636
(166)
7769
(490)
1757
(111)
5121
(323)
XR
6967
(440)
25105
(1584)
3483
(220)
10411
(657)
2322
(147)
6943
(438)
XS
5740
(362)
22961
(1449)
2870
(181)
8386
(529)
1913
(121)
5534
(349)
XS
7900
(498)
28470
(1796)
3950
(249)
11627
(734)
–
–
X2
4769
(301)
19074
(1203)
2384
(150)
8923
(563)
1590
(100)
5891
(372)
X2
4969
(313)
17905
(1130)
2484
(157)
8952
(565)
1656
(104)
5968
(377)
X3
5637
(356)
22549
(1423)
2819
(178)
10296
(650)
1879
(119)
6820
(430)
X3
6487
(409)
23378
(1475)
3244
(205)
11689
(737)
2162
(136)
7793
(492)
X4
6281
(396)
25125
(1585)
3141
(198)
11250
(710)
2094
(132)
7470
(471)
X4
8099
(511)
29185
(1841)
4049
(255)
14441
(911)
–
–
ZQ
4769
(301)
19076
(1204)
2385
(150)
6671
(421)
1590
(100)
4390
(277)
ZQ
6241
(394)
22491
(1419)
3121
(197)
8878
(560)
2080
(131)
5899
(372)
ZR
5272
(333)
21087
(1330)
2636
(166)
7318
(462)
1757
(111)
4820
(304)
ZR
6967
(440)
25105
(1584)
3483
(220)
9814
(619)
2322
(147)
6536
(412)
ZS
5740
(362)
22961
(1449)
2870
(181)
7907
(499)
1913
(121)
5214
(329)
ZS
7900
(498)
28470
(1796)
3950
(249)
10978
(693)
–
–
Z1
3959
(250)
15836
(999)
1980
(125)
7122
(449)
1320
(83)
4686
(296)
Z1
4138
(261)
14912
(941)
2069
(131)
7435
(469)
1379
(87)
4914
(310)
Z2
4769
(301)
19074
(1203)
2384
(150)
8427
(532)
1590
(100)
5559
(351)
Z2
4969
(313)
17905
(1130)
2484
(157)
8866
(559)
1656
(104)
5880
(371)
Z3
5637
(356)
22549
(1423)
2819
(178)
9748
(615)
1879
(119)
6450
(407)
Z3
6487
(409)
23378
(1475)
3244
(205)
11332
(715)
2162
(136)
7567
(477)
Z4
6281
(396)
25125
(1585)
3141
(198)
10672
(673)
2094
(132)
7077
(447)
Z4
8099
(511)
29185
(1841)
4049
(255)
13715
(865)
–
–
Содержание YK
Страница 4: ...JOHNSON CONTROLS FORM 160 75 EG1 519 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 18: ...JOHNSON CONTROLS FORM 160 75 EG1 519 18 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 59: ...FORM 160 75 EG1 519 JOHNSON CONTROLS 59 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 83: ...FORM 160 75 EG1 519 JOHNSON CONTROLS 83 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 91: ...FORM 160 75 EG1 519 JOHNSON CONTROLS 91 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 113: ...FORM 160 75 EG1 519 JOHNSON CONTROLS 113 THIS PAGE INTENTIONALLY LEFT BLANK...