FORM 160.87-OM1
ISSUE DATE: 8/24/2018
JOHNSON CONTROLS
32
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
OVERVIEW
This screen displays a cutaway view of the chiller con-
denser. All setpoints relating to the condenser side of
the chiller are maintained on this screen. Animation in-
dicates condenser liquid flow. This screen also serves
as a gateway to controlling the Refrigerant Level.
DISPLAY ONLY
Leaving Condenser Liquid Temperature
Displays the water temperature as it leaves the con-
denser.
Entering Condenser Liquid Temperature
Displays the water temperature as it enters the condenser.
Condenser Saturation Temperature
Displays the saturation temperature in the condenser.
Condenser Small Temperature Difference
Displays the difference between the Condenser Refrig-
erant temperature and the Leaving Condenser Liquid
temperature. The Condenser Refrigerant temperature
will be represented by the Condenser Saturation tem-
perature.
Condenser Pressure
Displays the refrigerant pressure in the condenser.
Condenser Liquid Flow Switch (Open/Closed)
Displays the status of the flow switch in the standard
condenser tube bundle.
Drop Leg Refrigerant Temperature
Displays the temperature of the refrigerant in the drop
leg between the condenser and evaporator shells, if the
sensor is present.
Sub-Cooling Temperature
Displays the difference between the Condenser Re-
frigerant temperature and the Drop Leg Refrigerant
temperature. The Condenser Refrigerant temperature
will be represented by the Condenser Saturation tem-
perature. If the Drop Leg Sensor is not present, this
temperature is not displayed.
High Pressure Switch (Open / Closed)
Displays the present position of the high pressure
switch. This will indicate whether a high pressure fault
is present.
CONDENSER SCREEN
LD22045
FIGURE 9 -
CONDENSER SCREEN