FORM 160.87-OM1
ISSUE DATE: 8/24/2018
JOHNSON CONTROLS
142
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
OVERVIEW
This screen displays a listing of the last 75 setpoint
changes. They are listed and numbered in reverse or-
der in which they were changed, with the most recent
listed as number 1. Multiple pages are necessary to dis-
play all 75 changes. Not all setpoints are logged.
The details of any setpoint change can be viewed by
navigating to a subscreen that displays the date and
time of the change, access level and User ID used to
make the change, the old setpoint value and the new
setpoint value.
Requires a login access level of SERVICE.
DISPLAY ONLY
Category
Displays the category of the setpoint (motor, evapora-
tor, condenser, etc.).
Setpoint
Displays the setpoint that was changed.
New Value
Displays the value that was entered at the time of the
setpoint change.
PROGRAMMABLE
Log Entry
Allows the user to select a particular setpoint change
for detail viewing.
Generates a detailed report of all setpoint changes list-
ed in the setpoint change log.
Page Up
Scroll up in the displayed data (if applicable).
Page Down
Scroll down in the displayed data (if applicable).
SECURITY LOG SCREEN
00662VIP
FIGURE 60 -
SECURITY LOG SCREEN