JOHNSON CONTROLS
21
FORM 155.31-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
3
SECTION 3 – HANDLING, STORAGE, INSTALLATION AND REASSEMBLY
LD18119
FIGURE 3 -
WARNING
Rigging and lifting should only be done by
a professional rigger in accordance with a
written rigging and lifting plan. The most
appropriate rigging and lifting method
will depend on job specific factors, such as
the rigging equipment available and site
needs. Therefore, a professional rigger
must determine the rigging and lifting
method to be used, and it is beyond the
scope of this manual to specify rigging
and lifting details
.
This chiller is for air conditioning or a cooling manu-
facturing process. Transport, store, and use this chiller
under the following conditions:
Installation location: Indoor, non-explosion area
Ambient temperature: 50 ~ 104 °F
Humidity:
10 ~ 90% (RH%)
Altitude:
3333 feet or lower
If the temperature in the plant room drops below 50 °F,
you must have the cold ambient option.