SECTION 4 - TECHNICAL DATA
FORM 155.32-ICOM2.EN.UL
ISSUE DATE:1/10/2018
78
JOHNSON CONTROLS
Communication Data
Table 24 -
Read Command
ITEM
DISPLAY
UNIT
ADDRESS
CONTENT
SET VALUE
1
Set Point (Chilled/Hot water outlet
temp.)
44.6
7
°F
°C
00001
0050~1000 unit, 1 unit=0.1°F (0.1°C)
2
Automatic stop temp. at cooling
mode (thermo-off temp)
41.0
5
°F
°C
00003
0040~1000 unit, 1 unit=0.1°F (0.1°C)
3
Temp. difference of Automatic start/
stop control at cooling mode
41.0
5
°F
°C
00005
0001~1000 unit, 1 unit=0.1°F (0.1°C)
4
Automatic stop temp. at heating
mode (thermo-off temp)
143.6
62.0
°F
°C
00007
0040~1000 unit, 1 unit=0.1°F (0.1°C)
5
Temp. difference of Automatic start/
stop control at heating mode
41.0
5
°F
°C
00009
0001~1000 unit, 1 unit=0.1°F (0.1°C)
OPERAT
ION CONDIT
ION
6
Operation condition
0 or 1 or 2
-
00021
0:STOP, 1:COOLING OPERATION, 2:HEATING
OPERATION
7
Local/Remote mode condition
0 or 1
-
01001
0:LOCAL, 1:REMOTE
8
Solution pump condition
0 or 1
-
01003
0:STOP,1:OPERATION
9
Refrigerant pump condition
0 or 1
-
01005
0:STOP,1:OPERATION
10
Burner fan condition
0 or 1
-
01007
0:STOP,1:OPERATION
11
Load limit condition
0 or 1
-
01009
0:NORMAL OPERATION
1:LOAD LIMIT OPERATION
12
Control manipulated variable
100
%
00023
-0100~1100 unit, 1 unit=0.1%
13
Failure signal
0 or 1
-
01011
0:NORMAL OPERATION
1:FAILURE OCCUR
14
Alarm signal
0 or 1
-
01013
0:NORMAL OPERATION
1:ALARM OCCUR
MEASUREMENT VA
LUE
15
Chilled/Hot water inlet temp.
53.6
12
°F
°C
00083
0001~4000 unit, 1 unit=0.1°F (0.1°C)
16
Chilled/Hot water outlet temp.
44.6
7
°F
°C
00085
0001~4000 unit, 1 unit=0.1°F (0.1°C)
17
Refrigerant temp. at evaporator
41.0
5
°F
°C
00087
0001~4000 unit, 1 unit=0.1°F (0.1°C)
18
Cooling water inlet temp.
89.6
32
°F
°C
00089
0001~4000 unit, 1 unit=0.1°F (0.1°C)
19
Cooling water outlet temp.
98.6
37
°F
°C
00091
0001~4000 unit, 1 unit=0.1°F (0.1°C)
20
Absorber solution temp.
100.4
38
°F
°C
00093
0001~4000 unit, 1 unit=0.1°F (0.1°C)
21
High temperature generator solution
temp.
293.0
145
°F
°C
00095
0001~4000 unit, 1 unit=0.1°F (0.1°C)
22
Exhaust gas temp.
428.0
226
°F
°C
00097
0001~4000 unit, 1 unit=0.1°F (0.1°C)
23
High temperature generator
pressure
10.15
70.0
mmHg
kPa
00099
0001~1100 unit, 1 unit=0.1 mmHg (0.1 kPa)
24
Motor opening rate
100.0
%
00101
0001~1100 unit, 1 unit=0.1%
25
High temperature generator
concentration
62.0
%
00103
0001~1100 unit, 1 unit=0.1%
26
Purge tank pressure
15
2.0
mmHg
kPa
00105
0001~4000 unit, 1 unit=0.1 mmHg (0.1 kPa)
Содержание YHAU-CGH
Страница 14: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 14 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 38: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 38 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 55: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 JOHNSON CONTROLS 55 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 57: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 57 LD27463...
Страница 59: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 59 LD27465...
Страница 61: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 61 LD27471...
Страница 63: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 63...
Страница 65: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 65 LD27477...
Страница 67: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 67 LD27479...
Страница 69: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 69 LD27475...
Страница 160: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 160 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 170: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 170 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 172: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 172 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 181: ...FORM 155 32 ICOM2 EN UL APPENDIX 1 CHECKLIST ISSUE DATE 1 10 2018 JOHNSON CONTROLS 181 NOTES...