JOHNSON CONTROLS
73
SECTION 6 – OPERATION
FORM 155.33-ICOM2.EN.GB
ISSUE DATE:12/4/2017
6
DATA SCREEN
FIGURE 27 -
DATA SCREEN
LD21529
The Data screen Measured Values section shows the
following:
Chilled / Hot Water Inlet Temp.:
temperature of the
chilled / hot water measured as it enters the evaporator
Chilled / Hot Water Outlet Temp.:
temperature of the
chilled / hot water measured as it leaves the evaporator
Cooling Water Inlet Temp.:
temperature of the cool-
ing water measured as it enters the absorber
Cooling Water Outlet Temp.:
temperature of the
cooling water measured as it leaves the condenser
Evaporator Refrigerant Temp.:
temperature of the
refrigerant in the evaporator
Absorber Temp.:
temperature of the diluted solution
in the absorber
HT-HEX Solution Outlet Temp.:
temperature of the
concentrated solution measured as it leaves the high
temperature solution heat exchanger
XG Generator Temp.:
temperature of the concentrat-
ed solution in the high temperature generator
XG Generator Pressure:
pressure in the high tem-
perature generator
Waste Hot Water Inlet Temp.:
temperature of the
waste hot water measured as it enters the waste hot wa-
ter heat exchanger
Waste Hot Water Out. Temp.:
temperature of the
waste hot water measured as it leaves the waste hot
water heat exchanger
Engine Waste Gas Inlet Temp.:
temperature of the
engine waste (exhaust) gas measured as it enters the
high temperature generator
Engine Waste Gas Out. Temp.:
temperature of the
engine waste (exhaust) gas measured as it leaves the
high temperature generator
Waste Gas Bypass Damper:
control output to the
waste gas bypass damper shown as a percentage
Purge Tank Pres:
pressure in the purge tank
Содержание YHAU-CE-JE Series
Страница 10: ...JOHNSON CONTROLS 10 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 22: ...JOHNSON CONTROLS 22 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 120: ...JOHNSON CONTROLS 120 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 135: ...JOHNSON CONTROLS 135 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 9 THIS PAGE INTENTIONALLY LEFT BLANK...