SECTION 5 - COMMISSIONING
FORM 155.33-ICOM2.EN.GB
ISSUE DATE:12/4/2017
5
EG input preparation
starts
Air purge damper close
operation starts
Inlet damper open
operation starts
Air purge blower stops
No
FIGURE 22 -
EXHAUST GAS INPUT PREPARATION FLOW DIAGRAM
Chiller-heater stops with
failure alarm
No
Chiller-heater stops with
failure alarm
Yes
Inlet and outlet damper
open limit signal
detected?
Air purge damper
close limit signal
detected?
No
Chiller-heater stops with
failure alarm
Bypass damper open
limit signal detected?
Temperature control with
EG bypass damper starts
30 seconds
passed?
No
Outlet damper open
operation starts
Yes
Exhaust gas
input delay time
passed?
No
Yes
Yes
EG input preparation
completed
Yes