JOHNSON CONTROLS
54
FORM 155.33-ICOM2.EN.GB
ISSUE DATE: 12/4/2017
SECTION 5 - COMMISSIONING
Remote or local
mode selection
Chiller-heater
operating
EG input stops
Dilution starts
Local stop command ON
Local
Solution pumps and
refrigerant pump stop
FIGURE 21 -
COOLING STOP DIAGRAM
Failure alarm?
No
Remote stop command
ON
Remote
Yes
No
Dilution complete?
Yes
No
Temperature control with
HW three-way valve stops
Chilled / hot water pump and
cooling water pump stop
Failure without dilution?*
*The chiller-heater stops without dilution due to
the following alarms:
-
Solution Circulation Pump Abnormal
- Solution Spray Pump Abnormal
- Refrigerant Pump Abnormal
- Chilled / Hot Water Suspension
- Chilled Water Overcooled
- Refrigerant Overcooled
- Emergency Failure Interlock