JOHNSON CONTROLS
52
FORM 155.33-ICOM2.EN.GB
ISSUE DATE: 12/4/2017
SECTION 5 - COMMISSIONING
EG inlet temp
≥ EG input start
temp?
Chiller-Heater stops with
failure indication
No
(within 3 min.)
Cooling water
pump interlock ON?
Exhaust gas
forced bypass
switch OFF?
Bypass time
passed after engine
starts?
HW inlet temp
≥
HW input start
temp?
Temperature control with
HW three-way valve starts
Yes
No
Yes
No
Yes
Yes
No
No
D
A
B
Remote or local
mode selection
Turn on power source
Initialize self-check
mechanism
Failure activated?
Engine operated?
Chilled / hot water pump
interlock on?
Thermo OFF light ON?
Local operation ON
Remote operation ON
Chiller-Heater stops with
failure alarm
Remote
Local
No
Yes
Solution pumps and
refrigerant pump start
FIGURE 20 -
COOLING START DIAGRAM
Yes
Yes
Chiller-Heater stops with
failure alarm
No
(within 3 min.)
Yes
No
No
Yes
Yes